Puls QS5.241 Power Supply Guia De Especificação

Página de 26
 
 
QS5.241, QS5.241-A1
 
 
Q-Series 
24V,
 
5A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
24.12. O
PERATION ON 
T
WO 
P
HASES
 
The power supply can also be used on two-phases of a three-phase-system. 
Such a phase-to-phase connection is allowed as long as the supplying 
voltage is below 240V+10%. Use a fuse or a circuit breaker to protect the 
N input. The N input is internally not protected and is in this case 
connected to a hot wire. Appropriate fuses or circuit breakers are specified 
in section 24.4 “External Input Protection”. 
240V 
+10%
 max.
Fuse
L2
L1
L3
L
N
PE
Power Supply
AC
DC
internal
fuse
 
24.13. U
SE IN A 
T
IGHTLY 
S
EALED 
E
NCLOSURE
 
When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher 
than outside. In such situations, the inside temperature defines the ambient temperature for the power supply. 
The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure. 
The power supply is placed in the middle of the box, no other heat producing items are inside the box  
Enclosure: 
 
 
Rittal Typ IP66 Box PK 9516 100, plastic, 110x180x165mm 
Load:    
 
 
24V, 4A; (=80%) load is placed outside the box 
Input: 
   230Vac 
Temperature inside enclosure:  
44.3°C (in the middle of the right side of the power supply with a distance of 2cm) 
Temperature outside enclosure:   23.3°C 
Temperature rise: 
 
21.0K 
Mar. 2013 / Rev. 2.2 DS-QS5.241-EN 
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
25/26