Puls QS5.241 Power Supply Guia De Especificação

Página de 26
 
 
QS5.241, QS5.241-A1
 
 
Q-Series 
24V,
 
5A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
24.9.  D
AISY 
C
HAINING OF 
O
UTPUTS
 
Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current 
through one terminal pin does not exceed 13A. If the current is higher, use a separate distribution terminal block as 
shown in Fig. 24-7. 
 
Fig. 24-6   Daisy chaining of outputs 
 
Fig. 24-7   Using distribution terminals 
 
Power
Supply
+  +
-  -
Input
Output
Load
+
-
max 13A!
Power
Supply
+  +
-  -
Input
Output
 
 
Load
+
-
Distribution
Terminals
Power
Supply
+  +
-  -
Input
Output
Power
Supply
+  +
-  -
Input
Output
 
 
24.10. S
ERIES 
O
PERATION
 
Unit A
AC
DC
Unit B
AC
DC
-
+
-
+
Load
+
-
Earth
(see notes)
Power supplies of the same type can be connected in series for higher 
output voltages. It is possible to connect as many units in series as needed, 
providing the sum of the output voltage does not exceed 150Vdc. Voltages 
with a potential above 60Vdc are not SELV any more and can be dangerous. 
Such voltages must be installed with a protection against touching.  
Earthing of the output is required when the sum of the output voltage is 
above 60Vdc.  
Avoid return voltage (e.g. from a decelerating motor or battery) which is 
applied to the output terminals.  
Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power 
supplies on top of each other. Do not use power supplies in series in mounting orientations other than the standard 
mounting orientation (input terminals on bottom and output terminals on the top of the unit).  
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies. 
 
24.11. I
NDUCTIVE AND 
C
APACITIVE 
L
OADS
 
The unit is designed to supply any kind of loads, including unlimited capacitive and inductive loads. 
Mar. 2013 / Rev. 2.2 DS-QS5.241-EN 
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
24/26