Puls QS5.241 Power Supply Guia De Especificação

Página de 26
 
 
QS5.241, QS5.241-A1
 
 
Q-Series 
24V,
 
5A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
6.  O
UTPUT
 
 
Output voltage 
nom. 
24V 
 
Adjustment range 
min. 
24-28V 
guaranteed 
 max. 
30V 
***)
 
at clockwise end position of potentiometer 
Factory setting 
typ. 
24.1V  
±0.2%, at full load, cold unit 
Line regulation 
max. 
20mV 
60-300Vac 
Load regulation 
max. 
100mV 
static value, 0A Æ 5A 
Ripple and noise voltage 
max. 
50mVpp 
20Hz to 20MHz, 50Ohm 
Output current  
nom. 
5A 
continuously available at 24V, see Fig. 6-1
 nom. 
4.5A 
continuously 
available at 28V, see Fig. 6-1
 
nom. 7.5A
 *)
 
short term available BonusPower
® *)
,  
at 24V, for typical 4s, see Fig. 6-1
 
nom. 6.7A
 *)
 
short term available BonusPower
® *)
,  
at 28V, for typical 4s, see Fig. 6-1
Output power 
nom. 
120W / 126W 
continuously available at 24V / 28V 
 
nom. 
180W / 188W 
*)
 
short term available BonusPower
® *)
 at 24V / 28V 
BonusPower
® 
time typ. 
4s  duration 
until 
the output voltage dips, see Fig. 6-2
 
 min. 
3s 
 
 max. 
5s 
 
BonusPower
® 
recovery time 
typ. 
7s 
overload free time to reset power manager, see Fig. 6-3
Overload behaviour 
 
cont. current 
 
Short-circuit current 
min. 
4A 
**)
 
continuous, load impedance 200mOhm, see Fig. 6-1
 max. 
7A 
**)
 
continuous, load impedance 200mOhm, see Fig. 6-1
 
 min. 
8A 
**)
 during 
BonusPower
® *)
, load impedance 200mOhm 
 max. 
13A 
**)
 during 
BonusPower
® *)
, load impedance 200mOhm 
 max. 
7A 
**)
 
continuous, load impedance <10mOhm, see Fig. 6-1
Output capacitance 
typ. 
3 500μF 
included inside the power supply 
*)  
BonusPower®, short term power capability (up to typ. 4s) 
The power supply is designed to support loads with a higher short-term power requirement without damage or shutdown. The short-
term duration is hardware controlled by an output power manager. This BonusPower
®
 is repeatedly available. Detailed information 
can be found in chapter 24.1. If the power supply is loaded longer with the BonusPower
®
 than shown in the Bonus-time diagram (see 
Fig. 6-2), the max. output power is automatically reduced to 120/126W.  
**) 
Discharge current of output capacitors is not included. 
***) 
This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not 
guaranteed value which can be achieved. The typical value is about 28.6V. 
 
Peak current capability (up to several milliseconds) 
The power supply can deliver a peak current which is higher than the specified short term current. This helps to start 
current demanding loads or to safely operate subsequent circuit breakers. 
The extra current is supplied by the output capacitors inside the power supply. During this event, the capacitors will be 
discharged and causes a voltage dip on the output. Detailed curves can be found in chapter 24.2
Peak current voltage dips  
typ. 
from 24V to 20V 
at 10A for 50ms, resistive load 
 
typ. 
from 24V to 20V 
at 20A for 2ms, resistive load 
 
typ. 
from 24V to 16V 
at 20A for 5ms, resistive load 
 
Mar. 2013 / Rev. 2.2 DS-QS5.241-EN 
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
6/26