Puls QS5.241 Power Supply Guia De Especificação
QS5.241, QS5.241-A1
Q-Series
24V,
5A,
S
INGLE
P
HASE
I
NPUT
3. AC-I
NPUT
AC input
nom.
AC 100-240V
suitable for TN-, TT- and IT mains networks
AC input range
min.
85-264Vac
continuous operation
min.
60-85Vac
full power for 200ms, no damage between 0 and 85Vac
min.
264-300Vac
<
500ms
Allowed voltage L or N to earth
max.
264Vac
continuous, IEC 62103
Input frequency
nom.
50–60Hz
±6%
Turn-on voltage
typ.
82Vac
steady-state value, see Fig. 3-1
Shut-down voltage
typ.
78Vac
steady-state value, see Fig. 3-1
typ.
58Vac
dynamic
value
AC 100V
AC 120V
AC 230V
Input current
typ.
1.34A
1.10A
0.62A
at 24V, 5A, see Fig. 3-3
Power factor *)
typ.
0.99
0.99
0.91
at 24V, 5A, see Fig. 3-4
Crest factor **)
typ.
1.48
1.55
1.71
at 24V, 5A
Start-up delay
typ.
120ms
110ms
85ms
Rise time
typ.
18ms
18ms
18ms
typ.
38ms
38ms
38ms
Turn-on overshoot
max.
100mV 100mV 100mV
*)
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range
Fig. 3-2 Turn-on behavior, definitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
P
OUT
60V
300Vac
264V
Shut
-down
full
power
for
200ms
Start-up
delay
Rise
Time
Ov
ersh
oot
- 5%
Output
Voltage
Voltage
Input
Voltage
Voltage
Fig. 3-3 Input current vs. output load at 24V
Fig. 3-4 Power factor vs. output load
5A
0.5 1 1.5 2 2.5 3 3.5 4 4.5
0
0.2
0.4
0.6
0.8
1.0
1.2
1.4A
Output Current
Input
Current, typ.
Current, typ.
230V
ac
120
Va
c
10
0V
ac
Power Factor, typ.
0.5
1 1.5 2 2.5 3 3.5 4 4.5 5A
0.75
0.8
0.85
0.9
0.95
1.0
Output Current
100Vac
120Vac
230V
ac
Mar. 2013 / Rev. 2.2 DS-QS5.241-EN
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/26