Puls QS20.241 Power Supply Guia De Especificação

Página de 26
 
 
QS20.241, QS20.241-A1, QS20.241-C1
 
 
Q-Series 
24V,
 
20A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
12.  T
ERMINALS AND 
W
IRING
 
 
Bi-stable, quick-connect spring clamp terminals. Shipped in open position. 
- IP20 Finger safe construction. 
- Suitable for field- and factory installation. 
 
Input Output 
DC-OK-Signal 
Type 
spring-clamp terminals 
spring-clamp terminals spring-clamp 
terminals 
Solid wire 
0.5-6mm
2
 0.5-6mm
2
 0.3-4mm
2
 
Stranded wire 
0.5-4mm
2
 0.5-4mm
2
 0.3-2.5mm
2
 
American Wire Gauge 
20-10 AWG 
20-10 AWG 
26-12 AWG 
Wire stripping length 
10mm / 0.4inch 
10mm / 0.4inch 
6mm / 0.25inch 
Max. wire diameter 
(including ferrules) 
2.8mm 2.8mm 2.25mm 
 
Fig. 12-1     Connecting a wire 
Instructions: 
a) Use appropriate copper cables that are designed for minimum 
operating temperatures of:  
60°C for ambient up to 45°C and  
75°C for ambient up to 60°C minimum 
90°C for ambient up to 70°C minimum. 
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal 
connection!  
d) Do not use the unit without PE connection. 
e) Unused terminal compartments should be securely tightened. 
f) Ferrules are allowed. 
 
1. Insert the wire
2. Close the lever
To disconnect wire:
reverse the procedure
 
 
 
 
Daisy Chaining of Outputs: 
Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current 
through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block as 
shown in Fig. 12-3. 
 
 
Fig. 12-2   Daisy chaining of outputs 
 
Fig. 12-3   Using distribution terminals 
 
Power
Supply
+  +
-  -
Input
Output
Load
+
-
max 25A!
Power
Supply
+  +
-  -
Input
Output
 
 
Load
+
-
Distribution
Terminals
Power
Supply
+  +
-  -
Input
Output
Power
Supply
+  +
-  -
Input
Output
 
 
 
Oct. 2013 / Rev. 2.2 DS-QS20.241-EN 
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 