Power supplies from the same series (Q-Series) can be paralleled to increase 
the output power. The output voltage shall be adjusted to the same value 
(±100mV) with the same load conditions on all units, or the units can be left 
with the factory settings.  
If more than three units are connected in parallel, a fuse or circuit breaker 
with a rating of 30A or 32A is required on each output. Alternatively, a diode 
or redundancy module can also be utilized. 
Keep an installation clearance of 15mm (left / right) between two power 
supplies and avoid installing the power supplies on top of each other. Do not 
use power supplies in parallel in mounting orientations other than the standard mounting orientation (input terminals 
on bottom and output terminals on the top of the unit) or in any other condition where a derating of the output 
current is required (e.g. altitude, above 60°C, …). 
Unit A
AC
DC
Unit B
AC
DC
-
+
-
+
Load
+
-
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies. 
 
 
22.8.  P
ARALLEL 
U
SE FOR 
R
EDUNDANCY
 
Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a 
certain amount of extra power to support the load in case one power supply unit fails. The simplest way is to put two 
power supplies in parallel. This is called a 1+1 redundancy. In case one power supply unit fails, the other one is 
automatically able to support the load current without any interruption. 
Redundant systems for a higher power demand are usually built in a 
N+1 method. E.g. five power supplies, each rated for 20A are paralleled 
to build a 80A redundant system. For N+1 redundancy the same 
restrictions apply as for increasing the output power, see also section 
22.7
24V
20A
Load
L
N
PE
Failure
Monitor
YR40.242
*)
Redundancy
Module
Input
1
Input
2
Output
+
-
+
-
+
-
I
I
*) 
YR40.241
also possible
+ +
- -
QS20.241
Power
Supply
24V,20A
DC-
OK
L   N  PE
+ +
- -
QS20.241
Power
Supply
24V,20A
DC-
OK
L   N  PE
Please note: This simple way to build a redundant system does not 
cover failures such as an internal short circuit in the secondary side of 
the power supply. In such a case, the defective unit becomes a load for 
the other power supplies and the output voltage can not be maintained 
any more. This can be avoided by utilizing decoupling diodes or Mosfets, 
which are included in the redundancy module YR40.241 or YR40.242. 
Recommendations for building redundant power systems: 
a) 
Use separate input fuses for each power supply. 
b) 
Monitor the individual power supply units. Therefore, use the DC-
OK relay contact of the QS20 power supply. 
c) 
It is desirable to set the output voltages of all units to the same 
value (± 100mV) or leave it at the factory setting. 
Oct. 2013 / Rev. 2.2 DS-QS20.241-EN 