Moxa ioLogik E1212 Guia De Especificação

Página de 5
Remote I/O
2
w w w. m o x a . c o m
ioLogik E1212 Specifications
ioLogik E1211 Specifications
ioLogik E1210 Specifications
Inputs and Outputs
Digital Inputs: 16 channels
Isolation: 3k VDC or 2k Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP), Dry Contact
I/O Mode: DI or Event Counter
Dry Contact: 
• On: short to GND 
• Off: open
Wet Contact (DI to COM): 
• On: 10 to 30 VDC  
• Off: 0 to 3 VDC
Inputs and Outputs
Digital Outputs: 16 channels
Isolation: 3k VDC or 2k Vrms
Digital Output
Type: Sink
I/O Mode: DO or Pulse Output
Pulse Output Frequency: 500 Hz
Over-Voltage Protection: 45 VDC
Over-Current Protection: 2.6 A (4 channels @ 650 mA)
Inputs and Outputs
Digital Inputs: 8 channels
Configurable DIOs (by jumper): 8 channels
Isolation: 3k VDC or 2k Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP), Dry Contact
I/O Mode: DI or Event Counter
Dry Contact: 
• On: short to GND 
• Off: open
Wet Contact (DI to COM): 
• On: 10 to 30 VDC  
• Off: 0 to 3 VDC
Common Type: 8 points per COM
Counter Frequency: 250 Hz
Digital Filtering Time Interval: Software Configurable
Common Type: 8 points per COM
Counter Frequency: 250 Hz
Digital Filtering Time Interval: Software configurable
Power Requirements
Input Voltage: 12 to 36 VDC
Input Current: 110 mA @ 24 VDC
MTBF 
(mean time between failures)
Time: 671,345 hrs
Standard: Telcordia SR332
Over-Temperature Shutdown: 175°C (typical), 150°C (min.)
Current Rating: 200 mA per channel
Power Requirements
Input Voltage: 12 to 36 VDC
Input Current: 200 mA @ 24 VDC
MTBF 
(mean time between failures)
Time: 923,027 hrs
Standard: Telcordia SR332
Digital Output
Type: Sink
I/O Mode: DO or Pulse Output
Pulse Output Frequency: 500 Hz
Over-Voltage Protection: 45 VDC
Over-Current Protection: 2.6 A (4 channels @ 650 mA)
Over-Temperature Shutdown: 175°C (typical), 150°C (min.)
Current Rating: 200 mA per channel
Power Requirements
Input Voltage: 12 to 36 VDC
Input Current: 155 mA @ 24 VDC
MTBF 
(mean time between failures)
Time: 561,930 hrs
Standard: Telcordia SR332
For Modbus devices that are controlled and 
detected by fixed addresses, users need to 
spend a vast amount of time researching 
and verifying initial configurations. Users 
need to locate each device’s networking 
details, such as I/O channels or vendor-
defined addresses, to enable the initial or 
start address of a SCADA system or PLC. 
The ioLogik E1200, with user-definable 
Modbus/TCP addressing, offers greater 
flexibility, and setup is easy. Instead of 
worrying about individual devices, users 
simply configure the function and address 
map to fit their needs.
User-Definable Modbus/TCP Addressing for Painless Upgrading of Existing Systems