Moxa ioLogik E1212 Guia De Especificação

Página de 5
Remote I/O
3
w w w. m o x a . c o m
ioLogik E1214 Specifications
Inputs and Outputs
Digital Inputs: 6 channels
Relays: 6 channels
Isolation: 3k VDC or 2k Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP), Dry Contact
I/O Mode: DI or Event Counter
Dry Contact: 
• On: short to GND 
• Off: open
Wet Contact (DI to COM): 
• On: 10 to 30 VDC  
• Off: 0 to 3 VDC
Common Type: 6 points per COM
Counter Frequency: 250 Hz
Digital Filtering Time Interval: Software configurable
Relay
Note: Ambient humidity must be non-condensing and remain between 5 and 
95%. The relays of the ioLogik E1214 may malfunction when operating in high 
condensation environments below 0°C.
Type: Form A (N.O.) power relay
Contact Current Rating: 
Resistive Load: 5 A @ 30 VDC, 250 VAC, 110 VAC
Breakdown Voltage: 500 VAC
Relay On/Off Time: 1500 ms (max.)
Initial Insulation Resistance: 1000 mega-ohms (min.) @ 500 VDC
Mechanical Endurance: 5,000,000 operations
Electrical Endurance: 100,000 operations @ 5 A resistive load
Contact Resistance: 100 milli-ohms (max.)
Pulse Output: 0.3 Hz at rated load
Power Requirements
Input Voltage: 12 to 36 VDC
Input Current: 188 mA @ 24 VDC
MTBF 
(mean time between failures)
Time: 808,744 hrs
Standard: Telcordia SR332
Inputs and Outputs
Analog Inputs: 8 channels
Isolation: 3k VDC or 2k Vrms
Analog Input
Type: Differential input
Resolution: 16 bits
I/O Mode: Voltage / Current (jumper selectable)
Input Range: 0 to 10 VDC, 0 to 20 mA, 4 to 20 mA, 4 to 20 mA 
(burnout detection)
Accuracy: 
±0.1% FSR @ 25°C 
±0.3% FSR @ -10 and 60°C 
±0.5% FSR @ -40 and 75°C
ioLogik E1240 Specifications
Sampling Rate: 
• All channels: 12 samples/sec 
• Per channel: 1.5 samples/sec 
• Only one channel enabled: 12 samples/sec
Input Impedance: 10 mega-ohms (min.)
Built-in Resistor for Current Input: 120 ohms
Power Requirements
Input Voltage: 12 to 36 VDC
Input Current: 121 mA @ 24 VDC
MTBF 
(mean time between failures)
Time: 474,053 hrs
Standard: Telcordia SR332
Inputs and Outputs
Digital Inputs: 8 channels
Digital Outputs: 4 channels
Configurable DIOs (by jumper): 4 channels
Isolation: 3k VDC or 2k Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP), Dry Contact
I/O Mode: DI or Event Counter
Dry Contact: 
• On: short to GND 
• Off: open
Wet Contact (DI to COM): 
• On: 10 to 30 VDC 
• Off: 0 to 3 VDC
Common Type: 12 points per COM
Counter Frequency: 250 Hz
Digital Filtering Time Interval: Software configurable
Digital Output
Type: Source
I/O Mode: DO or Pulse Output
Pulse Output Frequency: 500 Hz
Over-Voltage Protection: 41 VDC
Over-current Protection: 1.5 A per channel @ 25°C
Over-Temperature Shutdown: 175°C (typical), 150°C (min.)
Current Rating: 500 mA per channel
Power Requirements
Output Voltage Rating: 15 to 30 VDC (12 or 9 VDC configurable by 
jumper on the 4 DO channels)
Input Voltage: 12 to 36 VDC
Input Current: 130 mA @ 24 VDC
MTBF 
(mean time between failures)
Time: 715,256 hrs
Standard: Telcordia SR332
ioLogik E1213 Specifications
ioLogik E1241 Specifications
Inputs and Outputs
Analog Outputs: 4 channels
Isolation: 3k VDC or 2k Vrms
Analog Output
Resolution: 12 bits
Output Range: 0 to 10 VDC, 4 to 20 mA
Drive Voltage: 10 mA (max.)
Accuracy: 
±0.1% FSR @ 25°C 
±0.3% FSR @ -40 and 75°C
Load Resistor: Internal register, 400 ohms
Note: 24 V of external power required when loading exceeds 1000 ohms.