Panamax MB850 Manual Do Proprietário

Página de 4
3.
TO REPLACE THE BATTERY
  
1. Turn off and unplug all connected equipment.
  2. Turn the UPS off and unplug it from the AC power source.
  3. Turn the UPS upside down.
  4. Remove the retaining screws.
  5. Slide the battery compartment cover completely off of the unit.
  6. Remove the battery from the compartment.
  7. Disconnect the battery wires from the battery.
  8. Install the replacement battery by connecting the red wire to the positive (+) pole and black 
wire to the negative (-) pole of the battery.
  9. Put the battery back into the compartment.
10. Slide back the battery compartment cover and tighten the retaining screw.
11. Recharge the UPS for 8-16 hours to fully charge the battery.
REMINDER: Batteries are consider HAZARDOUS WASTE and must be disposed of properly. Almost any 
retailer that sells lead-acid batteries collects used batteries for recycling, as required by most state laws.
DEFINITIONS FOR ILLUMINATED LCD INDICATORS
INPUT voltage meter: This meter measures the AC voltage that the UPS
system is receiving from the utility wall outlet. The UPS is designed, through the 
use of automatic voltage regulation, to continuously supply connected equipment 
with stable, 110/120 output voltage. In the event of a complete power loss, severe 
brownout, or over-voltage, the UPS relies on its internal battery to supply 
consistent 110/120 output voltage. The INPUT voltage meter can be used as a 
diagnostic tool to identify poor-quality input power.
OUTPUT voltage meter: This meter measures, in real time, the AC voltage that the 
UPS system is providing to the computer, such as normal line mode, AVR mode, 
and battery back up mode.
Note: The OUTPUT voltage meter shows the status of the battery back up
outlets.
ESTIMATE RUN TIME: This displays the run time estimate of the UPS with the 
current battery capacity and load.
NORMAL icon: This icon appears when the UPS is working under normal 
conditions.
BATTERY icon: During a severe brownout or blackout, this icon appears and an 
alarm sounds (two short beeps followed by a pause) to indicate the UPS is 
operating from its internal batteries. Projection televisions should be turned off 
immediately. During a prolonged brownout or blackout, the alarm will sound 
continuously (and the BATT.CAPACITY meter shows one 20% capacity segment 
shaded) to indicate the UPS’s batteries are nearly out of power. You should save 
files and turn off your equipment immediately.
AVR (Automatic Voltage Regulator) icon: This icon appears whenever your UPS 
is automatically correcting too low or too high AC line voltage without using 
battery power. This is a normal, automatic operation of your UPS, and no action 
is required on your part.
SILENT MODE icon:This icon appears whenever the UPS is in silent mode. The 
buzzer does not beep during silent mode until the battery reaches low capacity.
OVER LOAD icon: This icon appears and an alarm sounds to indicate the 
battery-supplied outlets are overloaded. To clear the overload, unplug some of 
your equipment from the battery-supplied outlets until the icon turns off and the 
alarm stops.
FAULT icon: This icon appears if there is a problem with the UPS. Contact 
Panamax customer support for further help.
BATT. CAPACITY meter: This meter displays the approximate charge level (in 20% 
increments) of the UPS’s internal battery. During a blackout or severe brownout, 
the UPS switches to battery power, the BATTERY icon appears, and the charge 
level decreases.
LOAD CAPACITY meter: This meter displays the approximate output load level 
(in 20% increments) of the UPS’s battery outlets.
REPLACING THE BATTERY
CAUTION! Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the 
battery. Service the battery under the supervision of personnel knowledgeable of batteries 
and their precautions.
CAUTION! Use only the specified type of battery. See your dealer for replacement batteries.
CAUTION! The battery may present a risk of electrical shock. Do not dispose of battery in a 
fire as it may explode. Follow all local ordinances regarding proper disposal of batteries. 
Almost any retailer that sells lead-acid batteries collects used batteries for recycling, as 
required by most state laws.
CAUTION! Do not open or mutilate the batteries. Released electrolyte is harmful to skin and 
eyes and may be toxic.
CAUTION! A battery can present a high risk of short circuit current and electrical shock. 
Take the following precautions before replacing the battery:
1. Remove all watches, rings or other metal objects.
2. Only use tools with insulated handles.
3. Do not lay tools or metal parts on top of battery or any terminals.
4. Wear rubber gloves and boots.
5. Determine if the battery is inadvertently grounded. If grounded, remove the source of ground. 
CONTACT WITH A GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK!
The LCD display indicates a variety of UPS operational conditions. All descriptions apply 
when the UPS is plugged into an AC outlet and turned on or when the UPS is on battery.