Hytronik Electronics Co. Ltd HC418VRF Manual Do Utilizador

Página de 4
I –  10%
II –  20%
III – 30%
IV – 50%
Settings for HC424RF 
Stand-by period (corridor function)
This is the time period you would like to keep at the  low light output level before it is completely switched off in the long absence of people. 
I –  0S
II – 10S
III – 1 minute
IV – 5 minutes
V – 10 minutes
VI– 30 minutes
VII– 1 hour
VIII– +∞
+
0S
10S
1min 
5min 
10min 
30min 
1h

II
III
IV
V
VI
VII
VIII
1     2    3
Stand-by dimming level
This is the dimmed low light output level you would like to have after the hold-time in the absence of people. 
10%
20%
30%
50%
I  
II 
III 
IV 
1     2   
RF grouping (max. 10 channels)
Using  a screwdriver to adjust the rotary switch on both the master & slave unit, to keep them pointing at the same channel, the grouping is then 
automatically completed. 10 channels (max. 10 groups) available for both the master & slave unit.  
Using a screwdriver to point the arrow to the same position on the master unit and slave units.   
master
slave
SECTION 4 RF GROUPING
SECTION 5 FUNCTIONS
5.1 100H burn-in mode for fluorescent lamp
With simple operation, rapidly turn off/on the fixture 3 cycles wihin 3 sec. (the green LED on the sensor flashes and the fixture 
blinks 3 times to indicate the success of setup), lamp will be 100% on for 100 hours, and then automatically goes to sensor mode
after 100 hours. This is crucial to secure the lifetime of fluorescent lamp, when new fixture is installed,or old lamp is replaced.
This 100h burn-in feature can be cancelled by turn off/on the fixture 1 cycle within 1 sec.
With simple operation, rapidly turn off/on the fixture 2 cycles within 2 sec:
a. the green LED on the sensor flashes slowly for 5 seconds, meanwhile the fixture blinks twice.
b. the daylight sensor measures and remembers the surrounding lux for 1 sec.
c. the fixture and green LED is on for 10s to indicate the success of learning.
5.2 Ambient daylight threshold
This feature enables the fixture to function well in any real application circumstance, where the daylight penetrated
into fixture may vary a lot.
The latest surrounding lux value overwrites previous lux value learned. 
Both the setting on DIP switch and the learned ambient lux threshold can overwrite each other.The latest action stays in validity. 
*
 
*
 
*
 
Note: “0s” means on/off control; “+∞” means 2 steps of dimming control, fixture never switch off.