Murata Electronics North America HN1010 Manual Do Utilizador

Página de 58
HN-1010 Outdoor Base/Remote Station 
8  
HopNet Family of Products 
M-2410-0010, Rev - 
 
Data throughput is RS-485 Hybrid or RS-232 while flow control signals are single-
ended RS-232. Factory default is RS-485 Hybrid. RS-232 is selectable through 
internal user configurable jumpers.   
Jumper Settings 
The HN-1010 is shipped from the factory as an RS-485 Hybrid device. To change the 
interface to the RS-232 option the following tasks must be performed: 
−  Remove Top cover. 
−  Change jumper settings so that J11, J12, J13 and J15 only are inserted 
−  Replace top cover. 
The RS-232 option allows the HN-1010 to operate as a true RS-232 device 
 
 
Power Connection 
You can operate the HN-1010 from any well-filtered 7.5 to 24 VDC power source. 
The power supply should be capable of providing 750 mA peak current. Power 
connects through the 9-pin connector.  A polyfuse on the transceiver board protects 
against short circuits. 
Antenna Connection 
The RF signal is brought in on a standard female TNC jack connector located on the 
front panel. Use the following guidelines when installing the antenna: 
•  Be sure to strictly follow the antenna manufacturer’s installation instructions for 
proper operation of the antenna.  
1  Transmit Data 
(TXD+) 
4  Receive Data (RXD-) 
7  Data Carrier Detect 
(DCD) 
2  Transmit Data 
(TXD-) 
5  Clear to Send (CTS) 
8  VCC 
3  Receive Data 
(RXD+) 
6  Data Terminal Ready 
(DTR) 
9  Ground 
Jumper Configuration of HN-1010