Nokia Solutions and Networks T4KJ1 Manual Do Utilizador

Página de 157
LTE eNodeB Indoor Hardware Installation
BCUII installation
BCUII installation
Procedure 4-1
Adjusting Mounting Ears
1
Adjust the side ears as follows:
NOTE
The BCUII and all other LTE frame equipment can be mounted into
the rack in a forward or rearward position. The PDU, BCUII, and
Radio Filter Shelf are provided with mounting ears installed, so
that these components are in the forward position in the rack.
If desired, the mounting ears can be changed, so the BCUII resides in the
rear position within the rack.
1.
Disassemble the left and right mounting ears from the BCUII side
brackets using a T10 driver.
2.
Reinstall the left and right mounting ears on the BCUII side bracket at
the front position using a T10 driver. Torque the M3 screws to 1.12
N-m (10 in-lb) .
NOTE
The left mounting ear goes to the right side and the right mounting
ear goes to the left side.
Perform the steps in
to install power cables to the BCUII.
Procedure 4-2
Cabling Power to BCUII
1
Strip each wire 12.7 mm (1/2 inch).
2
Insert wires according to the color code on the back of the BCUII. Tighten
the screws to 1.3 N-m (12 in-lb). See
3
Plug the black 2-pin connector into the front of the PDU Brkr 1.
Route the cable with the green screw terminal connector towards the rear
over the left mounting ear.
4
Thread the cable through the slot in the left side bracket just behind the
plastic housing and across the rear of the PDU.
5
Install the BCUII in the rack.
NOTE
The power cable must be plugged into BCUII during the BCUII
installation procedure.
68P09308A55-6
4-3
FEB 2010