TDC-0971-011 CCU 100 and Repeater 100 Installation Guide 
83 
 
Proprietary and Confidential 
 
By combining Itron’s proven 900MHz ERT® platform with fixed network technology 
and software applications, Itron provides a suite of data collection technologies for 
electric, gas, and water utilities. This fixed network solution, which is built upon our 
ChoiceConnect® system architecture, enhances customer engagement, increases 
operational efficiencies, and ensures system integrity. 
The endpoints transmit to an Itron installed collection engine (data server) that is installed 
at the customer site, via one of three Itron manufactured network devices: a 
ChoiceConnect Tower Mounted Collector Unit (TCU 100), a ChoiceConnect Collector 
Unit (CCU 100) or a ChoiceConnect Repeater Unit (Repeater 100). 
A remote 900 MHz antenna can be configured instead of the standard vertically polarized 
antenna that is directly attached to the CCU/Repeater. The remote configuration uses a 
standard vertically polarized antenna (MSE-0330-001 – Standard 5dBi antenna – Antenna 
Products 1009-0066-403) that is connected remotely or a high-gain vertically polarized 
remote antenna (MSE -0372-001 – Hi Gain 8.15 dBi antenna – Laird FG9026) that is 
mounted remotely. 
Remote antennas must be properly grounded using a lightning arrestor. Refer t
 on page 93 for additional grounding information. 
 
Anritsu Site Master Calibration 
For the Antenna Line Sweeps procedure, Itron recommends using the Anritsu Site Master 
S331E, but similar models can be used. 
 
To set up and calibrate the Anritsu Site Master S331E 
1.  Set resolution to the maximum value (typical sweeps should be set to sweep values of 
902-928 MHz, with a propagation velocity of 0.8 and resolution of 517 points for the 
Anritsu Site Master). 
2.  Ensure all cables and jumpers are in their permanent locations and positions. Hangers, 
cable blocks, ground kits, and other hardware must be in place and connected using 
industry-standard torque wrenches to meet specifications for connectors. 
3.  Allow the test equipment to stabilize for approximately 15 minutes before taking any 
measurements. 
4.  Calibrate according to the manufactures instruction using a phase stable cable, 
precision 50 ohm load, open, and short circuit terminations. 
Note  Equipment must be calibrated per manufacturer suggested calibration period. 
Record the test equipment manufacturer, model number, and calibration expiration 
date on the 
A
P P E N D I X  
E  
Antenna Line Sweeps Procedure