Itron Inc. CCU100T Manual Do Utilizador

Página de 64
 
 CCU 100 and Repeater 100 Installation Guide 
 
53 
 
Proprietary and Confidential 
 
Status Indicator 
The LED Status Indicator is primarily intended to support installation personnel for 
immediate feedback. The following sequences define the Fixed Network solution's 
operational characteristics:  
1.  Each status sequence is repeated at 20 second intervals. The following status 
indicators are enabled at power-up or upon a communication failure with endpoints or 
backhaul.   
Initial power-on and CPU has initialized, but neither endpoint or backhaul 
communication has started: Morse "P" (
●  ▬ ▬ ●)  
2.  Super Raptor radio is seeing bubble-up endpoints but has not connected to the 
backhaul: Morse "N" (
▬ ●)  
3.  Backhaul radio is communicating, but no communication from endpoints: Morse "B" ( 
▬ ● ● ●)  
4.  Connected to backhaul radio & receiving endpoint packets: Morse "BN" ( 
▬ ● ● ● ▬ 
● )  
After 15 minutes of successful communication with backhaul and endpoints following 
a power-up (or communication failure), the sequence changes to LED on for 10 mSec, 
at 60 second intervals. This will continue until the next power-up.  
Sequence details: The dot time: 100 mSec 
The dash time is 300 mSec  
Off Time between B and N: 700 mSec  
Off time between dot and dash: 100 mSec 
A
P P E N D I X  
B  
Status and Diagnostics