Itron Inc. FNCCU4 Manual Do Utilizador

Página de 58
DRAFT
Chapter 3 - Installing the CCU4 Collector
21
Installation Procedure Summary
2. If you did not already do so to verify power, remove the photoelectric sensor, and insert
the power cable plug adapter into the socket.
3. Replace the photoelectric sensor, taking care to restore the sensor window to its original
orientation.
4. Wrap any excess cable around the davit or use tie-wraps (not included) to secure the cable
away from the unit.
5. Connect the other end of the power cable to the 5-pin power connector on the collector.
6. Verify the streetlight still works by covering the photoelectric sensor window with your
hand.
Figure 11:
Connecting the Collector to the Photoelectric Sensor
Connecting the Collector to the Secondary Power Wires 
To power the collector when installing it on a wood pole, you must strip the power cable with
wire strippers and connect the individual wires to the 120V and neutral wires on the pole. You do
not need to connect the power cable to earth ground because the collector housing is sealed and
plastic, and all electrical connections from the collector are fully isolated.
Photoelectric
Sensor
Power Adapter
Power
Connector