S ec ti o n   2 . 3 :   C h a n g i n g   O t h e r  N T 9 0 10   F u n c t i o n s
3 7
ing on page 27). Typically this zone is used for interior protection devices, 
such as motion detectors.
[06]
Delay Stay/Away Zone: This zone type will operate the same as the Inte-
rior Stay/Away zone type except that it will always provide entry delay. Typi-
cally this zone is used for interior protection devices, such as motion 
detectors, and will help prevent false alarms since it will always provide the 
user the entry delay time to turn off the system.
[07] - [09] For future use
[10]
24 Hour Supervisory Buzzer Zone:   Whether armed or disarmed, when 
this zone type is violated the system will immediately latch the keypad 
buzzer until a valid access code is entered and will communicate immedi-
ately to the central station.
[11]
24 Hour Burglary Zone:   If this zone is violated, whether armed or dis-
armed, the system will immediately latch the alarm output and communi-
cate to the central station. The alarm will sound for the Bell Cutoff time 
programmed in Section [005] “System Times” or until a valid access code is 
entered.
[12]-[20]:
The following zone definitions operate similar to the 24 Hour Burglary 
except for System Event output type, SIA identifier, and some zone 
attributes:
[12] 24 Hour Holdup Zone
[13] 24 Hour Gas Zone
[14] 24 Hour Heat Zone
[15] 24 Hour Medical Zone
[16] 24 Hour Panic Zone
[17] 24 Hour Emergency Zone
[18] 24 Hour Sprinkler Zone
[19] 24 Hour Water Flow Zone
[20] 24 Hour Freezer Zone
NOTE:
 [12] 24 Hour Holdup zones give a silent alarm by default.
[21]
24 Hour Latching Tamper:   If this zone is violated the installer must enter 
Installer Programming before the system can be armed. The bell output will 
also activate for the programmed time and the system will communicate 
the alarm.
[22]
Momentary Keyswitch Arm Zone:   Momentary violation of this zone will 
alternately arm/disarm the system.
[23]
Maintained Keyswitch Arm Zone:   When this zone is violated, the sys-
tem will arm. When this zone is secured, the system will disarm.
NOTE:
Do not program wireless zones as [22] or [23] Keyswitch zones.
[24]
For future use
[25]
Interior Delay Zone: When the system is fully armed (i.e. away armed), 
this zone will follow the exit delay. It will also follow the entry delay, pro-
vided that a delay zone is tripped first. If the delay zone is not tripped first, a 
zone defined as “Interior Delay” will go into alarm instantly. When the sys-