N. V. Nederlandsche Apparatenfabriek NEDAP SF2 Manual Do Utilizador

Página de 20
 
 
4/2012 
T/R Single Feeding VC4 
- 1 - 
D300F Version 0.6 
General 
 
 
 
 
The Transmitter/Receiver Single Feeding (T/R SF) is used for identifying and feeding 
animals in a feed station. Three or four motors can be connected.  
 
3 outputs T/R art. nr. 9845062 
 
4 outputs T/R art. nr. 9863397 
This transmitter/receiver can also be used for a floor antenna in the feed station for 
leg respactors, see special chapter at the end. 
 
CPS4FSS   
The name of the EPROM for the standard feed station is CPS4FSS x.xx. 
 
Description of the code : Cattlecode Poiesz Single feeder VC4 Feed Station 
Standard, x.xx = version number.  
 
This VC4 Transmitter / Receiver can only identify responders with a fast code (X-
ponders and respactors) 
 
 
 
 
T/R-single 1 and T/R-single 2 
The T/R-single 2 is the new generation hardware for the T/R-single. The PCB has 
been re-designed in order to meet the new EMC demands in Europe. Furthermore, 
the board has been extended with a 4th motor connection. The motor connections 
are now fully protected against over-voltage and short circuiting. 
 
In this module, the existing generation Single feeder hardware will be referenced as 
T/R-single 1, to distinguish it from the redesigned version, the T/R-single 2. 
 
 
 
T/R-single 2 : new motor brake circuit 
On the T/R-single 2 PCB the motor control circuitry has been changed. The new 
motor connections include a common brake circuitry, that is used to slow motors 
down quickly.  
 
 
 
When an T/R-single 1 board is replaced by a T/R-single 2 board, please check 
the parking-position of the motors that are connected.  
 
For every motor connection (output), the use of the new brake circuit has to be 
enabled. This can be done by means of the “brake jumpers”. These jumpers to the 
left (“BRAKE” or “BR”) enables the brake system for the corresponding motor. The 
brake system should be enabled for an output only when a motor is connected to that 
output. When e.g. a solenoid, or a lamp is connected, the brake system must be 
disabled for that output. If the brake system is enabled e.g. for a connected lamp, 
and the lamp is switched on, this will interfere with the brake function of a motor, 
connected to another port. 
 
When over heated the brake circuit will switch off, the brake does not function 
anymore at that moment, when the temperature drops again, the brake function will 
restore itself. 
 
 
 
 
Compatibility Single 1 versus Single 2 
The T/R-single 2 PCB has been set up in such a manner, that all programs that run 
on the T/R-single 1 hardware, also run on the new board of T/R Single 2.