M OU NTING 
 
 
PA RTS   IN C LU DE D
 
+  
Enlighted Room Control
 
+  
One gang  wallplate with hidden 
mounting screws hardware
 
+  
2x  construction screws
 
+  
2x  spacers
 
 
 
TO O L S  N EED ED 
 
+  
Screwdriver
 
+  
Level
 
 
 
 
 
 
 
 
 
 
 
 
D I M E N S I O N S
 
32mm L x  65mm W  x 4mm H
 
INSTRUCTIONS
 
 
1. 
Align  the backplate with the  Room Control with arrow pointing up. Affix  to 
the  Room Control by firmly   tightening both screws.
 
2.  
Align  spacers to  the  Room Control. Place spacers against the back of the 
switch—one at  the  top  and  one  at  the  bottom—and  align the spacers with 
the  oval screw hole of  the mounting plate. Ensure flush side of  the spacers 
face the  wall.  Hold   in  place against desired wall location.
 
3.  
Screw on  backplate using  construction screws provided.
 
 
4.      Snap on  wallplate with arrow pointing  up.
 
 
TE CH N ICA L  S P E CI FIC ATIO N S
 
 
 
Action 
Four push buttons; six  software-configurable scenes
 
Actuations 
50,000 rated
 
Power  
Battery-powered: CR  2025
 
 
Battery Life 
5  years approximate
 
 
Max  Fixtures Per Switch 
100
 
 
Security 
AES-128  Encryption
 
 
Interoperability 
Enlighted Gen2 Sensors  and  Gateways
 
 
Radio Frequency 
2.4  GHz  ISM Band
 
 
RF  TX  Output Power 
0 dBm
 
 
Wireless Protocol  
IEEE  802.15.4
 
 
Wireless Range  
300  feet line-of-sight
 
 
Operating Environment 
0  to  50° C  / 32  to 120°  F
 
 
Enclosure 
Polycarbonate
 
 
CO M P LIA N CE
 
Wo rl dwid e 
RoHS,  IC
 
United States 
FCC  Class A  Part 15, UL  Listed
 
 
FCC  ID: AQQ-WS100; IC: 10138A-WS100
 
Warning:
 
This device complies  with Part  15 of  the FCC  Rules. Operation is  subject  to  the  following two conditions:  (1) this device may  not  cause  harmful 
interference, and  (2) this device must accept any interference received, including  interference that may cause undesired operation.
 
Changes  or modifications not  expressly approved by Enlighted Inc.  could void the user’s authority to operate the equipment.
 
This device complies  with Industry Canada  license-exempt  RSS  standard(s).  Operation  is  subject to the  following two conditions:  (1)  this  device 
may not cause interference, and  (2) this device must accept any interference, including  interference that may cause undesired operation of  the device.
 
Le présent appareil est conforme aux CNR  d’Industrie Canada  applicables  aux appareils radio exempts de licence. L’exploitation est autorisée 
aux deux conditions suivantes : (1)  l’appareil ne doit  pas  produire de brouillage, et  (2)   l’utilisateur de  l’appareil doit accepter tout brouillage
 
radioélectrique  subi, même si  le  brouillage est susceptible d’en compromettre le  fonctionnement.
 
 
 
 
 
930 Benecia Avenue, Sunnyvale CA  94085   |     P: 650.964.1094
 
©  Copyright 2013. All  Rights Reserved.
 
2