Página de 20
2 APD0602 A140513 Wireless CO Install
The Wireless Carbon Monoxide Alarm contains a sounder which generates 
the ANSI S3.41 temporal 4 pattern in an alarm condition (see Table 1 for 
temporal 4 pattern). In alarm, a message is also sent to the control panel 
and the detector’s ID is displayed at the console. During an alarm condition, 
pressing the detector’s hush button will silence the sounder for five minutes. 
The mounting base installation is simplified by the incorporation of features 
compatible for both drywall fasteners (not supplied) and other methods.
Tricolored LED (green, yellow, red) and a sounder on the detector provide 
local visual and audible indication of the detector’s status as listed in Table 1. 
During initial power-up the LED blinks alternately green, yellow then red. It 
takes about 60 seconds for the detector’s CO sensor to stabilize. 
After power-up has completed and the detector is functioning normally, the 
green LED blinks once every 12 seconds.
Status
LEDs
Sounder
(does not pulse 
the sounder and 
LED concurrently)
Radio
signalling
Normal
Green flash every 
12 seconds
Off
Normal
(None)
Alarm/ Test
Red flash every 
12 seconds
ANSI S3.41 
temporal 4 (press 
button to hush 
for 5 minutes)
Alarm
Detector
trouble
Yellow flash 
every 6 seconds
One 100ms chirp 
every 45 seconds
Fault
Low battery
Yellow flash 
every 12 seconds
One 100ms chirp 
every 45 seconds 
(press button 
to hush for 12 
hours)
Low Battery
Detector end 
of life
Yellow flash 
every 23 seconds
One 100ms chirp 
every 45 seconds
Fault
Powerup
Green, yellow, 
red flash 
sequence every 
12 seconds
One 100ms chirp 
at end of power-
up sequence
None
Tamper
Green, yellow, 
red flash 
sequence every 
12 seconds
Off
Tamper
Table 1. Detector status and indication