X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
13.1 Status
When the X75 is first accessed using a WEB browser the Controller Status page
shown below is displayed.
Figure 11 - Status WEB Page (typical)
The following describes the function of the different parts of the applet with the
exception of FACTORY SETTINGS which is reserved for UNIPOWER use.
At the top is the site name. This can be changed in the installation applet.
Next is the main system bus voltage. Note that this will always show as an unsigned
value even in systems that have a negative voltage with respect to chassis ground.
Next to the system voltage is an indicator of the state of the system. The various
possible indicators are as follows:
FLT
Indicates that the system is in float mode without any temperature
compensation.
TC
Indicates that the system is in float mode with temperature compensation
applied.
CHG
The system is bulk charging the batteries.
EQ
The system is equalizing or boosting the battery voltage.
BD
The system is in battery discharge.
TST
The system is performing a battery test.