To restore parameters that have been changed and not yet uploaded click on
REFRESH.
13.3.2 - Float & TC
Figure 14 - Installation WEB Applet - float & tc tab (typical)
The Float & TC tab is used to set up the voltage and temperature compensation of
the system as below:
Nominal System Float Voltage is the voltage that the system will output in the
absence of any current limiting, equalizing or temperature compensation. This
should be set to match the system battery requirements.
Temperature Compensation Slope. The controller applies straight line temperature
Temperature Compensation Slope. The controller applies straight line temperature
compensation to the system voltage in order to maintain the batteries at their optimal
charge state. Enter a figure here to match the requirements of the batteries.
Maximum Temperature for temperature compensation. If the battery temperature
Maximum Temperature for temperature compensation. If the battery temperature
rises above this setting, no further temperature compensation will be applied.
Minimum Temperature for temperature compensation. If the battery temperature
Minimum Temperature for temperature compensation. If the battery temperature
falls below this setting, no further temperature compensation will be applied.
Current for Float Mode ON. If the battery charging current falls below this
Current for Float Mode ON. If the battery charging current falls below this
level, the system will be considered to be in float charging mode (with or without
temperature compensation).
Current for Float Mode OFF. If the battery charging current rises above this level
Current for Float Mode OFF. If the battery charging current rises above this level