Unique Broadband Systems Ltd. DRU2KW User Manual

Page of 64
Page 31
X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
To restore parameters that have been changed and not yet uploaded click on  
REFRESH.
13.3.2 - Float & TC
Figure 14 - Installation WEB Applet - float & tc tab (typical)
The Float & TC tab is used to set up the voltage and temperature compensation of 
the system as below:
Nominal System Float Voltage is the voltage that the system will output in the 
absence of any current limiting, equalizing or temperature compensation.  This 
should be set to match the system battery requirements.
Temperature Compensation Slope.  The controller applies straight line temperature 
compensation to the system voltage in order to maintain the batteries at their optimal 
charge state.  Enter a figure here to match the requirements of the batteries.
Maximum Temperature for temperature compensation.  If the battery temperature 
rises above this setting, no further temperature compensation will be applied.
Minimum Temperature for temperature compensation.  If the battery temperature 
falls below this setting, no further temperature compensation will be applied.
Current for Float Mode ON.  If the battery charging current falls below this 
level, the system will be considered to be in float charging mode (with or without 
temperature compensation).
Current for Float Mode OFF.  If the battery charging current rises above this level 
the system will be considered to be in bulk charging mode.