X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
13.8 Data Log
Figure 30 - Data Log WEB Applet (typical)
The controller normally logs data once every 5 minutes (default). It logs the following
parameters:
• Voltage
• Rectifier Current
• Load Current
• Battery Current
• Battery Temperature 1
• Battery Temperature 2 (not used on X75)
• External Temperature
• Controller Temperature
• Number of rectifiers
• Analog 1-4 (not used on X75)
• Digital inputs (only digital input 1 is used on X75)
• Free RAM.
The log is able to hold 8640 records which allows for 30 days of continuous data
recording at 5 minute intervals.
The logging time can be adjusted to suit the application. The choices are: 1 minute,
5 minutes, 10 minutes, 30 minutes or 1 hour. This can be adjusted using the
Logging Time combo-box at the top of the applet. To send the updated selection
to the controller click the UPDATE LOGGING TIME button at the bottom. An