Parameter / UPS
Power supply parameters
Output parameters
Environmental parameters
Mechanical parameters
SINLINE PRO 10 000
Apparent/active power
Supply system topology
1P3W
1P3W
10 kVA
8 kW
230 V
230 V
46 A
44 A
50 Hz
80 A gG
80 A gG
80 A
<600 BTU
10
0
÷40 C
0
0
÷40 C
< 95 %
< 1000 m
200 kg
front: >200 mm
sides: >100 mm
 >300 mm
rear:
340x740x795mm
2
10mm
2
10mm
Rated voltage
Rated input frequency
Minimum wire section surface area
Minimum wire section surface area
Output system topology
Working temperature
Storage temperature
Humidity
UPS weight
Operating  distance
Altitude (above sea level)
Quantity of heat released for nominal 
work conditions
Device dimensions 
(width x depth x height)
Rated output voltage
Rated current
Rated current
P r i m a r y  
and  BYPASS 
line protection
Output  
line protection
Switch fuse
Switch fuse
Switch 
disconnector
CONNECTING THE UPS
The weight of the device should be considered when selecting the location for the installation. The UPS should only 
be used in rooms where dust, temperature, and humidity levels are within the device specifications. The appropriate 
device cooling conditions must be ensured for the UPS to work correctly. For this reason, the ventilation openings of 
the UPS must be uncovered at all times, and the distance between the UPS and other objects should not be less 
than 30 cm.
Detailed information is provided in a separate guidelines document that is enclosed with the product.
 
 
 
INSTALLATION GUIDELINES
SINLINE PRO 10 000