PROTECTION
Overload protection
An overload (above 105%) is indicated by a continuous sound and a corresponding message on the display.
If the overload is 105 ÷ 120%, then the power supply unit will remain in the previous mode for one minute before switching 
to BYPASS. If the overload exceeds 120% of the nominal power rating, the Bypass mode is switched on immediately. The 
unit  remains  in  BYPASS  as  long  as  the  overload  continues  above  the  predefined  limit  (CONFIGURATION  3/4; 
ProgKas.Prz.). Once the overload discontinues, the unit attempts to restart five times. If they fail, the unit switches to 
EMERGENCY mode. In BACKUP mode, an overload causes the unit to switch to EMERGENCY mode without any 
additional attempts to restart.
Short circuit protection
The presence of a short circuit is indicated by the 
corresponding message and a quick, intermittent sound. If the short circuit lasts longer than 100 ms, the unit is switched to 
EMERGENCY mode.
 
 
 
 
 
In the inverter-based modes, i.e. NORMAL, BACKUP, and HYBRID, there is an electronic short circuit protection that, in 
case of a short circuit, limits the short circuit current to a safe level. 
 
 In work modes where the BYPASS line is used, automatic fuses F3 are used. 
Surge protection
The unit features surge protection at the input, which protects the receiver circuits and internal circuitry against high 
energy voltage surges that are caused by atmospheric phenomena and interference in the power network.
Battery protection
Batteries  are  protected  with  fusible  cut-outs. The  connection  of  the  external  battery  pack  features  an  additional 
safeguard, as do the internal batteries. These safety devices also serve as disconnecting switches that can be used, for 
example.
The types of fuses are specified in the technical parameters table.
 
 
 during assembly. 
www.ever.eu
NOTE! It is forbidden to use fuses other than those listed in the device specification.
The  instructions  placed  in  the  frame,  below  the  fuses,  informing  about  the  need  to  maintain  an 
appropriate order when switching in fuses, must be followed. Switch on F1 at the beginning, and then 
wait 10 s and switch F2. Failure to follow these instructions may damage the unit.
 
 
The fusible cut-out F5 protects the terminal of the external battery pack and is located to the right of the 
terminals. When the mounting is open, both poles become disconnected.
 
Thermal protection
The unit is equipped with a thermal safeguard that protects it against overheating. There are two levels of protection. If the 
internal temperature approximates a critical value, then a sound is emitted and a message is displayed on the screen.
If the temperature keeps rising, at the critical value an alert message is displayed 
and the unit switches to EMERGENCY mode.
 
 
 
The unit remains in the current mode. 