GSI ELECTRONICS INC. EDGERFID Manual Do Utilizador

Página de 70
4
Troubleshooting
Problem
Solution
The KP-8IN-1REL or
TP-8IN-1REL or TR-
2IN-1REL does not
communicate
Verify if the controller is powered up
Verify if there is any activity on the communication bus by looking at the LEDs: AUTOMA-
TION-RX, AUTOMATION-TX, SAFETY-RX, SAFETY-TX.
Verify if the network link is installed correctly: Terminal A fromThe KP-8IN-1REL or TP-
8IN-1REL or TR-2IN-1REL to the Main Controller terminal A, Terminal B from The KP-
8IN-1REL or TP-8IN-1REL or TR-2IN-1REL to the Main Controller terminal B
Verify if the network communication is installed in daisy chain.
Verify if your end of line (EOL) are set correctly on your network.
Verify if the network link is cut (either the wire is cut or the protections are activated).
Verify if there is a short-circuit on the network link between terminal A and B.
Verify if the network link length is below 4000 feet (1200m) with the recommended gage.
Measure the voltage between terminal 24V and GND. The voltage must be at least 16V.
If the problem persists, contact your dealer or GSI Electronics.
The KP-8IN-1REL or
TP-8IN-1REL or TR-
2IN-1REL does not
power up
Verify if the LED "3.3V" or "5V" is activated on PCB-434.
Measure the voltage between terminal 24V and GND. The voltage must be at least 16V.
Verify if the power link is installed correctly: Terminal 24V from The KP-8IN-1REL or TP-
8IN-1REL or TR-2IN-1REL to the Main Controller terminal 24V, Terminal GND from The
KP-8IN-1REL or TP-8IN-1REL or TR-2IN-1REL to the Main Controller terminal GND.
Verify if the power link is cut (wire is cut).
Verify if the power link length is below 300 feet (1000m) with the recommended gage.
If the problem persists, contact your dealer or GSI Electronics.
The KP-8IN-1REL or
TP-8IN-1REL or TR-
2IN-1REL does not
still power up
Verify if the LED "3.3V" or "5V" is activated on PCB-434.
Measure the voltage between terminal 24V and GND. The voltage must be at least 16V.
Verify if the power link is installed correctly: Terminal 24V from The KP-8IN-1REL or TP-
8IN-1REL or TR-2IN-1REL to the Main Controller terminal 24V, Terminal GND fromThe
KP-8IN-1REL or TP-8IN-1REL or TR-2IN-1REL to the Main Controller terminal GND.
Verify if the power link is cut (wire is cut).
Verify if the power link length is below 300 feet (1000m) with the recommended gage.
If the problem persists, contact your dealer or GSI Electronics.
Relay does not acti-
vate the load
Verify if the LED 4 is activated on PCB-434.
Verify the wiring if the right contact is used correctly.
Verify if the load does not activate the protection. The current must be below 5A and
higher than 0.1A.
If there is an overload, find out the issue and solve it and reset the electronic fuse by
resetting it on the Main controller software.
895-00695