Connecting an alarm fixture 
  
Alarm relay 
The Industrial PoE Switch has dry relay contacts for connecting an external alarm fixture.  
Located on the green terminal block on the top panel, the relay has “normally open” contacts 
that can be wired to form a circuit for triggering an external alarm when a fault occurs (light or 
audible alarm)
.  See Figure 11.  
Note:
 
Normally open contacts are contacts that form an open circuit when there is a loss of 
power to the device or when a fault occurs.  Once power is applied to the Industrial 
PoE Switch, the contacts will be closed and current will flow through the contacts. 
 
 
 
Figure 11:  Alarm Relay Contacts 
  
Alarm relay 
wiring 
To wire an alarm to the relay contacts, do the following: 
Step 
Action 
1.   
Verify that the external power source is turned OFF. 
2.   
Strip the wires as required.  
3.   
Wire the alarm relay as shown in Figure 12. 
 
 
Figure 12:  Alarm Relay Wiring 
 
Continued on next page 
Alarm Relay Contacts