GALAXY 5000 AVAILABLE IN 40 kVA, 50 kVA, 60 kVA, 80 kVA, 100 kVA, OR 130 kVA (APPLIES TO PARAGRAPH 1.4A1). 
 
 
SINGLE MODULES ARE FIELD UPGRADEABLE TO PARALLEL MODULES (APPLIES TO PARAGRAPH 1.4A2). 
 
 
INVERTER OUTPUT IS TRANSFORMERLESS AND DOES NOT PROVIDE A NEUTRAL SINGLE-PHASE LOADS, A ∆Y 
VOLTAGE MATCHING TRANSFORMER IS REQUIRED (APPLIES TO PARAGRAPH 1.4A4). 
 
 
CHOOSE 208 VOLT AC, 220 VOLT AC, 480 VOLT AC, 600 VOLT AC (APPLIES TO PARAGRAPH 1.4B1). 
 
 
OUTPUT POWER RATINGS (APPLIES TO PARAGRAPH 1.4A1). 
40 kVA / 36 kW 
50 kVA / 45 kW 
60 kVA / 54 kW 
80 kVA / 72 kW 
100 kVA / 90kW 
130 kVA / 117kW 
 
 
480 VOLT CORE VOLTAGE (208 VOLT, 200 VOLT, 600 VOLT WITH INPUT TRANSFORMER) (APPLIES TO 
PARAGRAPH 1.4A2 AND PARAGRAPH 1.4A3). 
 
 
INPUT CURRENTS (APPLIES TO PARAGRAPH 1.4A5) 
 
40 kVA 
50 kVA 
60 kVA 
80 kVA 
100 kVA 
130 kVA 
A @ 480 volts AC 
Max – Charging 
Battery 
59 70 88 111 150 182 
 
 
OUTPUT CURRENTS (APPLIES TO PARAGRAPH 1.4A6) 
 
40 kVA 
50 kVA 
60 kVA 
80 kVA 
100 kVA 
130 kVA 
A @ 480 volts AC 
48 
60 
72 
96 
120 
156 
 
BATTERY BACK-UP TIME (APPLIES TO PARAGRAPH 1.4A7) 
  
(minutes) 
Configuration Battery 
40 
kVA  50 
kVA 
60 kVA 
80 kVA 
100 kVA 
130 kVA 
1 x Level 3 
NPX-150 
11 
1 x Level 4 
300 WPC 
28 
22 
16 
10 
1 x Level 5 
400 WPC 
41 
31 
24 
16 
11 
1 x Level 6 
500 WPC 
59 
46 
36 
25 
17 
11 
2 x Level 5 
400 WPC 
90 
72 
57 
41 
31 
22 
2 x Level 6 
500 WPC 
81 
58 
47 
33 
3 x Level 6 
500 WPC 
127 
94 
71 
54 
ADDITIONAL CONFIGURATION AND RUN TIMES ARE AVAILABLE
 
 
BATTERY DC CURRENT (APPLIES TO PARAGRAPH 1.4D2) 
 
40 kVA 
50 kVA 
60 kVA 
80 kVA 
100 kVA 
130 kVA 
ADC At Max 
End voltage 
109 137 164 219 273  355