Intel® Server System SR1640TH TPS 
Power Sub-System 
Revision 1.0 
 
 
69 
Intel order number: E94847-001 
3.7.1 
Power supply management controller (PSMC) 
The PSMC device in the power supply shall derive its power of the 5Vsb output on the 
system side of the O’ring device and shall be grounded to return.  
It shall be located at the address set by the A0 and A1 pins. 
Refer to the specification posted on 
 and 
 website for 
details on the power supply monitoring interface requirements and refer to followed section 
of supported features. The below table reflect the power module addresses complying with 
the position in the housing. 
 
3.7.2 
Power supply field replacement unit (FRU) signals 
The power supply shall support electronic access of FRU information over an I
2
C bus. Four 
pins at the power supply connector are allocated for this. They are named SCL, SDA, A0, A1. 
SCL is serial clock. SDA is serial data. These two bidirectional signals forms the basic 
communication lines over the I
2
C bus. A0, A1 are input address lines to the power supply. 
The backplane defines the state of these lines such that the address to the power supply is 
unique within the system. The resulting I
2
C address shall be per the table below. 
The device used for this shall be powered from a 5V bias voltage derived from the +5 VSB 
output . No pull-up resistors shall be on SCL or SDA inside the power supply.  
FRU data shall be stored starting in address location 8000h through 80FFh(ref). The FRU 
data format shall be compliant with the IPMI specifications. The current versions of these 
specifications are available at: 
 
3.7.3 
Power Supply Status LED indicators 
There will be a bi-color LED to indicate power supply status as shown below; 
Table 67. Power supply status 
Power supply condition 
Power supply LED 
No AC power to PSU 
OFF 
AC present/only standby output on 
Flashing GREEN 
Power supply DC output ON and OK 
GREEN 
Power supply failure 
RED 
Power supply warning 
Flashing RED/GREEN 
 
3.8  PSMC and PMBus compliance 
The PSMC monitoring and control function set shall comply to the PMBus Spec. Rev. 1.1 
and above, which can be downloaded from the 
.  
3.8.1 
Hardware 
The device in the power supply is compatible with both the SMBus 2.0 “high power” 
specification for I
2
C Vdd based power and drive (for Vdd = 3.3V). This bus operates at 3.3 V 
but is tolerant of 5 V signaling. It also operates at full 100 kbps SMBus speed without using 
clock stretching to slow down the bus. 
PDB position and power 
module address 
PM1/B0h 
PM2/B2h 
PM3/B4h 
PM4/B6h 
Pin A0 
0 1  0  1 
Pin A1 
0 0  1  1