 Electrical 
Installation 
Tester 
 Specifications 
53 
RCD Testing 
RCD Types Tested 
RCD Type
[6]
 
Model 1652C 
Model 1653B 
Model 1654B 
AC
[1]
 
G
[2]
 
 
 
 
AC S
[3]
 
 
 
 
A
[4]
 G 
 
 
 
A S 
 
 
 
B
[5]
 G 
 
 
 
B S 
 
 
 
Notes 
[1]  AC – Responds to ac 
[2]  G – General, no delay 
[3]  S – Time delay 
[4]  A – Responds to pulsed signal 
[5]  B – Responds to smooth dc 
[6]  RCD test inhibited for V 
>
265 ac 
 
RCD tests permitted only if the selected current, multiplied by earthing resistance, is <50 V. 
Test Signals 
RCD Type 
Test Signal Description 
AC 
(sinusoidal) 
The waveform is a sinewave starting at zero crossing, polarity 
determined by phase selection (0 
°
 phase starts with low to high zero 
crossing, 180 
°
 phase starts with high to low zero crossing). The 
magnitude of the test current is I
Δ
n x Multiplier for all tests. 

(half wave) 
The waveform is a half wave rectified sinewave starting at zero, 
polarity determined by phase selection (0 
°
 phase starts with low to 
high zero crossing, 180 
°
 phase starts with high to low zero crossing). 
The magnitude of the test current is 2.0 x I
Δ
n (rms) x Multiplier for all 
tests for I
Δ
n = 0.01A. The magnitude of the test current is 1.4 x I
Δ
(rms) x Multiplier for all tests for all other I
Δ
n ratings. 
B (DC) 
This is a smooth DC current according to EN61557-6 Annex A