55 
RCD/FI-Tripping Current Measurement/Ramp Test (I
Δ
Dwell Time 
Current Range 
Step Size 
Type G 
Type S 
Measurement 
Accuracy 
30 % to 110 % of 
RCD rated current
[1]
  10 % of I 
Δ
 N
[2]
300 ms/step 
500 ms/step 
±
5 % 
Notes 
[1]  30 % to 150 % for Type A I
Δ N
 >10 mA 
30 % to 210 % for Type A I
Δ N
 = 10 mA 
20 % to 210 % for Type B 
Specified trip current ranges (EN 61008-1):  
50 % to 100 % for Type AC 
35 % to 140 % for Type A (>10 mA) 
35 % to 200 % for Type A (
10 mA) 
50 % to 200 % for Type B 
[2]  5% for Type B 
 
Earth Resistance Test (R
Models 1653B and 1654B Only. This product is intended to be used to measure 
installations in process plants, industrial installations, and residential applications. 
Range Resolution  Accuracy 
200 
Ω
 0.1 
Ω
 
±
(2 % + 5 digits) 
2000 
Ω
 1 
Ω
 
±
(3.5 % + 10 digits) 
 
Range: RE + R
PROBE
[1]
 Test 
Current 
2200 
Ω
 
3.5 mA 
16000 
Ω
 500 
μ
52000 
Ω
 150 
μ
Note 
[1]  Without external voltages 
 
Frequency Output 
Voltage 
128 Hz 
25 V 
 
Live Circuit Detection 
Inhibits test if terminal voltage >10 V ac is 