Testboy TV 455VDE-tester Testboy TV 455 Manual Do Utilizador

Códigos do produto
Testboy TV 455
Página de 76
TESTBOY TV 450 
Technical specification 
 
62 
9.2 Continuity 
 
9.2.1  Resistance R LOW
Ω 
 
Measuring range according to EN61557 is 0.16 
Ω ÷ 1999 Ω. 
Measuring range R (
Ω) Resolution 
(
Ω
Accuracy 
0.00 
÷ 19.99 
0.01 
±(3 % of reading + 3 digits)
20.0 
÷ 199.9 
0.1 
200 
÷ 1999 
±(5 % of reading) 
 
Open-circuit voltage...........................6.5 VDC 
÷ 9 VDC 
Measuring current..............................min. 200 mA into load resistance of 2 
Ω 
Test lead compensation.....................up to 5 
Ω 
The number of possible tests ............> 2000, with a fully charged battery 
Automatic polarity reversal of the test voltage.  
 
9.2.2  Resistance CONTINUITY (model TESTBOY TV 450 (TYPE B)) 
 
Measuring range (
Ω) Resolution 
(
Ω
Accuracy 
0.0 
÷ 19.9 
0.1 
20 
÷ 1999 
±(5 % of reading + 3 digits)
 
Open-circuit voltage...........................6.5 VDC 
÷ 9 VDC 
Short-circuit current ...........................max. 8.5 mA 
Test lead compensation.....................up to 5 
Ω 
 
9.3 RCD testing 
 
Note: 
All data (marked with “*”) regarding B type RCDs are valid for model TESTBOY TV 450 
(TYPE B) only. 
 
9.3.1 General data 
 
Nominal residual current (A,AC) ........10 mA, 30 mA, 100 mA, 300 mA, 500 mA,  
1000 mA 
Nominal residual current accuracy.....-0 / +0.1
⋅IΔ; IΔ = IΔN, 2×IΔN, 5×IΔN  
-0.1
⋅IΔ / +0; IΔ = 0.5×IΔN 
AS / NZ selected: ± 5 % 
Test current shape.............................Sine-wave (AC), pulsed (A), smooth DC (B)* 
DC offset for pulsed test current ........6 mA (typical) 
RCD type ...........................................G (non-delayed), S (time-delayed) 
Test current starting polarity ............. 0 º or 180 º 
Voltage range ....................................50 V 
÷ 264 V (45 Hz ÷ 65 Hz)