Finder 19.41.0.024.0000 Relay (Feedback) 1 NO contact/(contact) 1 CO contact 24V DC/AC IP20 19.41.0.024.0000 Ficha De Dados
Códigos do produto
19.41.0.024.0000
3
2 NO (SPST-NO) separate output
1/3
125/250
125
25
—
1/0.3/—
10 (0.1/1)
AgNi + Au
24
24
0.8 (50 Hz)/0.5
(0.8...1.1) U
N
(0.8...1.1) U
N
1,000
–20…+50
IP 20
Output specification
Contact configuration
Rated current/Maximum peak current
A
Rated voltage/Maximum switching voltageV AC
Rated load AC1
VA
Rated load AC15 (230 V AC)
VA
Single phase motor rating (230 V AC)
kW
Breaking capacity DC1 (24/110/220 V)
A
Minimum switching load
mW (V/mA)
Standard contact material
Input specification
Nominal voltage (U
N
)
V AC (50/60 Hz)
V DC
Rated power
VA (50 Hz)/W
Operating range
AC
DC
Technical data
Ambient temperature range
°C
Protection category
Approvals (according to type)
19 Series - Override & Status indicating modules
Features
2-channel status indicating module
•
2-channel indicating module to provide visual
indication of BMS/DDC/PLC input or output
status with immediate indication of its
importance or urgency according to the colour
of the LED. Two NO output contacts, following
the inputs to the module, provide for further
control or status feedback. Commonly used in
building management systems
indication of BMS/DDC/PLC input or output
status with immediate indication of its
importance or urgency according to the colour
of the LED. Two NO output contacts, following
the inputs to the module, provide for further
control or status feedback. Commonly used in
building management systems
•
24V AC/DC inputs
•
35 mm rail (EN 60715) mounting
Application examples:
•
status reports of heating installations, pumps,
blowers or motor groups
blowers or motor groups
•
error reports such as danger of frost or
blocked filter
blocked filter
•
fire alarm
•
LED indicator, 3 colours: Red, Green ,Blue
•
2 NO control
•
17.5 mm wide
19.32.0.024.0000
Wiring diagram
A3-A2 Channel 1: Control signal status
A4-A2 Channel 2: Control signal status
A4-A2 Channel 2: Control signal status
The LED colour is selected by the dip-switch on the rear face of the module, prior to mounting
on the 35 mm rail.
The colour is determined by the system designer according to the urgency or importance of
the signal.
Commonly, the following levels of importance or urgency are assigned to the Red, Green and
Blue colours according to EN 60073:
- Red LED: Error
- Green LED: In operation
- Blue LED: Alarm (fire or similar)
on the 35 mm rail.
The colour is determined by the system designer according to the urgency or importance of
the signal.
Commonly, the following levels of importance or urgency are assigned to the Red, Green and
Blue colours according to EN 60073:
- Red LED: Error
- Green LED: In operation
- Blue LED: Alarm (fire or similar)
For outline drawing see page 11
Controller, PLC
Type 19.32
Request
Response
* LED Signals
*
*
VI-2012, www
.finder