Finder 19.41.0.024.0000 Relay (Feedback) 1 NO contact/(contact) 1 CO contact 24V DC/AC IP20 19.41.0.024.0000 Ficha De Dados

Códigos do produto
19.41.0.024.0000
Página de 14
3
2 NO (SPST-NO) separate output
1/3 
125/250
125
25
1/0.3/— 
10 (0.1/1)
AgNi + Au
24
24
0.8 (50 Hz)/0.5
(0.8...1.1) U
N
(0.8...1.1) U
N
1,000
–20…+50
IP 20
Output specification
Contact configuration
Rated current/Maximum peak current 
A
Rated voltage/Maximum switching voltageV AC
Rated load AC1 
VA
Rated load AC15 (230 V AC)
VA
Single phase motor rating (230 V AC)
kW
Breaking capacity DC1 (24/110/220 V)
A
Minimum switching load
mW (V/mA)
Standard contact material
Input specification
Nominal voltage (U
N
)
V AC (50/60 Hz)
V DC
Rated power
VA (50 Hz)/W
Operating range
AC
DC
Technical data
Ambient temperature range
°C
Protection category 
Approvals (according to type)
19 Series - Override & Status indicating modules
Features
2-channel status indicating module
2-channel indicating module to provide visual 
indication of BMS/DDC/PLC input or output 
status with immediate indication of its 
importance or urgency according to the colour
of the LED. Two NO output contacts, following 
the inputs to the module, provide for further 
control or status feedback. Commonly used in 
building management systems
24V AC/DC inputs 
35 mm rail (EN 60715) mounting
Application examples:
status reports of heating installations, pumps, 
blowers or motor groups
error reports such as danger of frost or 
blocked filter
fire alarm
LED indicator, 3 colours: Red, Green ,Blue
2 NO control
17.5 mm wide
19.32.0.024.0000
Wiring diagram
A3-A2 Channel 1: Control signal status 
A4-A2 Channel 2: Control signal status 
The LED colour is selected by the dip-switch on the rear face of the module, prior to mounting
on the 35 mm rail.
The colour is determined by the system designer according to the urgency or importance of
the signal.
Commonly, the following levels of importance or urgency are assigned to the Red, Green and
Blue colours according to EN 60073: 
- Red LED: Error
- Green LED: In operation
- Blue LED: Alarm (fire or similar)
For outline drawing see page 11
Controller, PLC
Type 19.32
Request
Response
* LED Signals
*
*
VI-2012, www
.finder