Burnham C Series Ficha De Características

Página de 2
*8. Unit(s) shall be equipped with a Model _______ built-in tankless heater coil installed in the water space 
at the front of the boiler, with the capacity to heat _______ GPH of domestic water from 40F to 140F with 
boiler water at ____F. 
 
Fuel Burning Equipment: 
The burner(s) shall incorporate all necessary devices and controls to make a complete fuel burning system 
for the type of fuel specified herein, and bear the listing label of UL evidencing compliance with 
requirements of UL-296 for oil burners, and/or UL-795 for gas burners. 
 
*9a. Oil burners for #2 oil shall be of the forced-draft pressure atomizing type, complete with integral motor 
driven blower, oil pump, oil nozzle(s) oil solenoid valve(s), ignition assembly, combustion safeguard, motor 
starters, and all necessary controls for safe and efficient operation in accordance with UL requirements (and 
FM requirements)(and IRI requirements). 
 
Note: Insert additional details such as desired combustion safeguard, firing sequence, and/or other features 
to meet project specifications. 
 
*9b. Gas burners shall be of the forced draft multi-jet type suitable for burning ______ gas with heat 
content of ________ BTU per cubic foot and specific gravity of _____  delivered to the gas train inlet at a 
pressure of ( ________ inches w.c)( _______ psig).  Burner shall be complete with integral motor driven 
blower, ignition assembly, combustion flame safeguard, motor starter, complete gas train, including gas 
pressure regulator and dual gas valves, and all necessary controls for safe and efficient operation in 
accordance with UL requirements (and FM requirements)(and IRI requirements). 
 
Note: Insert additional details such as desired combustion safeguard, firing sequence, and/or other features 
to meet project specifications. 
 
*9c. Combination gas/oil burner shall consist of an integral assembly of a forced-draft pressure atomizing 
oil burner suitable for burning #2 oil and a forced draft multi-jet type gas burner suitable for burning _____ 
gas with a heat content of _____ btu per cubic foot and specific gravity of _____ delivered to the gas train 
inlet at a pressure of ( ______ inches w.c.)( ______ psig).  Burner shall be complete with integral motor 
driven blower, ignition assembly, combustion flame safeguard, motor starter, complete gas train, including 
gas pressure regulator and dual gas valves, oil pump, oil nozzle(s) oil solenoid valve(s), ignition assembly, 
combustion safeguard, motor starters, and all necessary controls for safe and efficient operation in 
accordance with UL requirements (and FM requirements)(and IRI requirements).  Changeover to either fuel 
shall be by means of manual selector switch which shall energize only those circuits necessary to provide 
the appropriate timing and sequence of events for the fuel selected, except that the oil pump may continue 
to operate when firing gas.  No burner adjustments or re-positioning of control linkage shall be required 
when changing from one fuel to an alternate fuel. 
 
Note: Insert additional details such as desired combustion safeguard, firing sequence, and/or other features 
to meet project specifications. 
   
10. Electrical supply to the boiler(s) will be _____ volts ______ hz _______ phase.  All control circuits 
shall be 120 volts, 60 hz, 1 phase with all switches in the ungrounded leg.  Fuse protection for the control 
circuit shall be provided. 