Vector 6SE70 VC Manual Do Utilizador

Página de 57
Page 22
Version 1.0    March 1, 2000
1.3.2  Volts/Hz with Encoder
Note:  Complete section 1.3.1 before operating the motor with encoder feedback.
P060 = 5
P100 = 0
P130 = ?
P151 = ?
P060 = 1
P060=5
Select “Drive Settings”
P100=0
Selects Volts/Hz
with Encoder Feedback
P130 = Select Type of Encoder
11: Pulse Encoder
15: Pulse Encoder with Zero Pulse
P151 = Pulse Per Revolution (PPR)
P060 = Return to Parameter Menu