10-Pump, 80-Station Controller           Chapter 6:  Configurable Settings 
66 
Name Description 
Options 
Default 
Every n loads 
Number of conveying cycles between filter 
cleanings. 
Adjust this setting based on experience. The 
more dust and debris in your material line, the 
smaller this number needs to be. 
1–99 5 
# pulses 
Number of pulses of compressed air sent 
through the station’s filter during cleaning. 
If blowback is not working as desired, the 
service department may ask you to change this 
setting.  
1–99 5 
On time 
Number of seconds that the each air pulse lasts 
during filter cleaning. 
If blowback is not working as desired, the 
service department may ask you to change this 
setting. 
0.1–99.9 sec.  1.0 sec. 
Off time 
Number of seconds between air pulses during 
filter cleaning. 
If blowback is not working as desired, the 
service department may ask you to change this 
setting. 
0.1–99.9 sec.  1.0 sec. 
Slide gate 
When this option is enabled, the controller 
opens the slide gate between the station and 
the receiver during the dump delay and during 
blowback. 
Enable this option if and only if the station has a 
slide gate instead of a flapper and demand 
switch. 
disabled, 
enabled 
disabled 
Purge 
When enabled, this option allows the system to 
empty the material line completely after every 
convey to this station. The station’s pump 
continues to draw without picking up material for 
an extra period of time after conveying is 
finished. 
Enable this option if and only if you are using a 
purge valve for this station. This option cannot 
be used with a volume-fill station. 
disabled, 
enabled 
disabled 
Purge duration 
Number of seconds allowed for purging. The 
station’s vacuum valve remains open for the 
convey time plus this time. 
Adjust this setting to the amount of time 
required for material to travel from the pickup 
point (purge valve) to the station. 
0–999 sec. 
20 sec. 
Purge valve 
Number (address) for the purge valve used with 
this station. 
Set this to match the number (address) for the 
purge valve that services this station. If another 
station has the purge valve that services this 
station, enter the number of that station (range: 
1–50). If a central purge valve services this 
station, enter the number (address) of that valve 
(range: 51–154). 
1–154 
0 (= not 
assigned) 
Material set to n 
Number for the material line that should be 
connected to this station. 
0 –150 
0 (= not 
assigned)