Tyco SafeLINC 4100U Manual Do Utilizador

Página de 180
 
6-8
 
 
The relays have one set of voltage-free contacts (see note below) connected to one pair of 
terminals via a header.  The two terminals are configured for normally closed or normally 
open by positioning a jumper on the header. 
 
Table 6-3. Alarm Relay Card Jumper Positions 
Relay Header 
Normally 
Closed Normally 
Open 
Alarm 
Isolate (Supervisory) 
Fault (Trouble) 
P1 
P2 
P3 
1-2 (top) 
1-2 (top) 
1-2 (top) 
2-3 (bottom) 
2-3 (bottom) 
2-3 (bottom) 
 
 
•  The common contact of each relay has a transient suppressor to earth, and must not be 
used to switch voltages greater than its rating. 
 
•  The common contact is protected with a 3A fuse. 
 
•  For default configuration the relays are normally de-energised and energise on 
Fault/Isolate/Alarm. 
 
•  The corresponding LED illuminates when the relay is energized. 
 
•  The relays may be configured under custom control to operate other than default. 
 
 
If relay RL3 is configured for operation other than Fault (Trouble), jumper P3 on the SPS 
must be shifted to positions 1-2 (top). 
 
 
 
CARD 
Input Voltage 
20-32Vdc 
Input Current 
15mA @ 24V, quiescent 
(nominal) 
37mA @ 24V, all relays on 
RELAYS 
Form 
Voltage-free changeover, suppresses to 
earth 
Voltage 30Vac, 
32Vdc 
Current 
2A, resistive load 
FUSE 
F1, F2, F3 
5 x 15mm, Glass Cartridge, 3A (208-163) 
 
 
 
The Alarm Relay Card, 
Continued
 
Configuration 
Notes 
Warning 
Specification