All the 4100U cards and modules (pcbs) are tested and aligned in the factory before being 
supplied to the customer or fitted to a FIP.  The only field adjustment that may be 
necessary is to set the battery charger voltage.  (Note this has been set and should not 
need re-adjusting). 
 
R341 
Battery Charger Voltage 
 
Should the battery charger voltage need adjusting, the method is as follows: 
 
1. 
Run the system with the batteries connected and the door closed for at least 30 
minutes to allow components to "warm up" (the longer the better). 
 
2. 
Calculate the required no-load battery charging voltage by taking 27.3V for 
20
°C and subtracting approximately 0.1V for every 3°C above 20°C, or adding 
approximately 0.1V for every 3
°C below 20°C. 
 
3. 
With the system not in Alarm, disconnect the batteries. 
 
4. 
Measure the voltage at the battery terminals and adjust to the voltage calculated 
in Step 2 by turning pot R341. 
 
5. 
Re-connect the batteries. 
 
 