Tyco SafeLINC 4100U Manual Do Utilizador

Página de 180
 
 
D-3 
 
 
This section describes how to conduct an Earth Fault Search, from selecting the 
appropriate access code to correcting the fault. 
 
The panel must be at the appropriate access level (1, 2, 3, or 4) in order to run diagnostics. 
To get to the correct access level, 
 
1.  Press the Menu button. The following message comes up (press the Next or 
Previous buttons, if necessary, to display it): 
 
Press <NEXT> or <PREVIOUS> to scroll 
Change Access Level? 
 
3.  Press the Enter button. Now you are prompted to log in or log out. 
 
1=Login   2=Logout 
CURRENT ACCESS LEVEL = x 
 
4.  Press the "1" key on the numeric keypad to log in, so that the passcode prompt 
comes up. 
 
Enter a Passcode followed by <ENTER> 
 
 
5.  Enter the passcode and press the Enter button. ACCESS GRANTED displays 
briefly on the LCD, and then the display goes back to: 
 
1=Login   2=Logout 
CURRENT ACCESS LEVEL = y 
 
You can now open the diagnostic menu as described in the next topic. 
 
To start an Earth Fault Search, 
 
1.  If necessary, press the Menu button to access the menus. 
6.  Press the Previous or Next buttons until the diagnostic functions option appears: 
 
Press <NEXT> or <PREVIOUS> to scroll 
Diagnostic Functions? 
 
7.  Press the Enter button. Then press Next or Previous buttons until the Earth Fault 
Search option appears: 
 
Press <NEXT> or <PREVIOUS> to scroll 
Earth Fault Search? 
 
Continued on next page 
Earth Fault Searching from the Front Panel 
Overview 
Access Level 
Selection 
Starting the Earth 
Fault Search