D-5 
 
 
If you select the IDNet Channel Search menu item, a list of IDNet channels to search 
becomes available. Use the Next and Previous buttons to scroll through the list. When the 
IDNet channel you want to search is shown and "Press <ENTER> to start search" 
displays, the search is ready to start. A sample screen is shown below. 
 
IDNET CHANNEL M12 
Press <ENTER> to select for search 
 
NOTE:  The FACP suspends normal operation for the duration of the 
search.
  
 
Press the Enter button to start the search. 
 
As the search progresses, watch the display for an indication of how much of the search 
has been completed. The search can be aborted at any time if you press the Clear button. 
 
Earth Search In-Progress, Please Wait... 
 
 
Earth Search In-Progress, Please Wait... 
                  40% 
 
Skip ahead to the "Completing the Search" topic. 
 
This option simply displays the last Earth Fault Search result. If there has been no search 
since the last system startup, or if the last search was aborted, the panel displays 
"RESULT NOT AVAILABLE." 
 
When a Location or IDNet Channel Search completes, all of the following occurs: 
•  All slaves automatically reset. 
•  The FACP turns off the Earth Fault Search trouble pseudo-point. 
•  The panel displays the specific fault information. 
 
The panel can only return one Earth Fault Search result at a time. If another fault exists, it 
can only be found via diagnostics after the first fault is cleared. Faults will continue to 
appear, one by one, until each one has been found and corrected. 
 
IMPORTANT: Once you have been directed to an earth ground fault and 
corrected it, it is recommended that you restart the system (warm- or cold-
start). 
 
Continue to the next topic for a list of search results and their required actions. 
 
 
 
Earth Fault Searching from the Front Panel, 
Continued
 
Search Option B:  
Select Channel 
Search Option C:  
Last Search Result 
Completing the 
Search