Tyco SafeLINC 4100U Manual Do Utilizador

Página de 180
 
 
F-4
 
Simplex MAPNET 2 Range – Addressable Field Devices 
 
 
 
2190-9156   
 
 
Mapnet 2 Monitor ZAM 
2190-9162   
 
 
Mapnet 2 Signal ZAM 
2190-9164   
 
 
Mapnet 2 Control ZAM 
2190-9169   
 
 
Mapnet 2 Line Powered Short Circuit Isolator 
2190-9172   
 
 
Mapnet 2 Supervised IAM 
2190-9173   
 
 
Mapnet 2  Loop powered 2 Point Input / Output 
Module 
4099-9032NL   
 
Mapnet 2 Addressable Manual Call Point 
 
 
 
 
 
The following lists the detectors approved for use with IDNet and shows current 
rating and numbers allowed per loop. 
 
Device Type 
Operating 
Current mA 
Maximum 
Number Allowed 
Per Loop 
Maximum 
Number 
Allowed Per 
Line 
4098-9714E 
Analogue Photoelectric 
Smoke Detector 
0.5  
(2 with LED 
on) 
250 40* 
4098-9717E 
Analogue Ionisation 
Smoke Detector 
0.5  
(2 with LED 
on) 
250 40* 
4098-9733E 
Analogue Heat Type A & 
B Detector 
0.5  
(2 with LED 
on) 
250 40* 
4098-9754E 
Analogue Multi 
(Heat/Photo) 
Detector 
0.5  
(2 with LED 
on) 
250 40* 
 
* Maximum allowed by AS1670.1. 
 
The above with 9714E, 9717E and 9733E use a (4098-) 9789E addressable base 
or 9794E addressable sounder base, or 9793 addressable isolator base.  The 
9754E uses a 9796E addressable base or 9795E sounder base. 
 
The maximum specified loop/line resistance is 40
Ω. 
 
The maximum number of LEDs switched on by an IDNet in alarm is 20. 
 
 
 
 
List of Approved Devices, 
Continued 
Compatible Detectors, IDNET