Tyco SafeLINC 4100U Manual Do Utilizador

Página de 180
 
 
F-5
 
 
 
The following lists the addressable devices approved for use with IDNet and 
shows current rating and numbers allowed per loop. 
 
Device Type 
Operating 
Current mA 
Maximum 
Addressable 
Point On 
Analogue Loop 
Maximum 
Addressable 
Points on 
Analogue Line 
4090-9116 
IDNet Comms Isolator 
0.5 
(2 with LED on) 
250 40* 
4090-9118 
Relay IAM with T-sense 
0.5 
(2 with LED on) 
250 40* 
4090-9117 
Addressable Power 
Isolator 
0.5 
(2 with LED on) 
250 40* 
4090-9118 
Relay IAM with T-Sense  
Input 
0.5 
(2 with LED on) 
250 40* 
4090-9119 
Relay IAM with 
unsupervised Input 
0.5 
(2 with LED on) 
250 40* 
409-9120 
6 Point I/O 
0.5 250 40* 
4090-9001 
Supervised IAM 
0.65 
(2.8 with LED 
on) 
250 40* 
4090-9101 
Monitor ZAM 
0.65 
(2.8 with LED 
on) 
250 40* 
4099-9032 
Manual Call Point 
0.65 
(2.8 with LED 
on) 
250 40* 
 
* Maximum allowed by AS1670.1. 
 
The maximum specified loop/line resistance is 40
Ω. 
 
The maximum number of LEDs switched on by an IDNet in alarm is 20. 
 
The 6 Point I/O LED is powered from the external 24V supply, not from the loop. 
 
Note:  The relays on the 6 Point I/O are not approved for switching field loads, 
i.e. the   
 
contacts may only be used to switch loads within an earthed 
cabinet. 
 
 
 
Compatible Addressable Field Devices, IDNet