Tyco SafeLINC 4100U Manual Do Utilizador

Página de 180
 
 
H-2
 
 
 
The DC input voltage range of the following modules is 18-33Vdc.  The current listed is 
nominal for 24Vdc, and may be used for battery capacity calculations. 
 
Module Name 
Quiescent 
Alarm 
N/A 
Master Controller Assembly  
(includes SPS, CPU, CPU Motherboard 
with RUI I/F, Operator Interface with 
LCD) 
373mA 470mA 
4100-6035 
Alarm Relay Card 
15mA 
37mA 
4100-3101 
IDNet Module without Devices 
per device add 
with 250 devices add 
75mA 
0.8mA 
200mA 
115mA 
1mA 
250mA 
4100-1289 
64/64 Controller plus Switch LED 
Modules 
   - no 
LED 
on 
   - per 
LED 
on 
add 
   - with 
64 
LEDs 
on 
add 
 
20mA 
3mA 
210mA 
 
 
3mA 
210mA 
4100-0620 Transponder 
Interface, Basic Unit 
87mA 
87mA 
4100-0625 Transponder 
Interface, Local Mode 
112mA 
112mA 
4100-6014 Network 
Interface Card 
28mA 
28mA 
4100-6056 Wired 
Media 
Module 
55mA 
55mA 
4100-6057 
Fibre Optic Media Module 
25mA 
25mA 
4100-6038 Dual 
RS232 
Interface 132mA 
132mA 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Voltage & Current Ratings of Modules & Assemblies