Tyco SafeLINC 4100U Manual Do Utilizador

Página de 180
 
 
J-1 
 
 
The IDNet cabling requirements are detailed in Chapter 8 of this manual. 
 
 
Line Characteristics 
 
Note: In the following paragraphs the term "MAPNET channel" is used to mean those 
lines connected to any one Mapnet Transceiver board. Parallel runs from the same board 
do not constitute separate channels. The term "continuous run" refers to the loop distance 
from the primary output, through all devices and back to the secondary output. 
 
Line characteristics are based on 0.58uF and/or 35 Ohms total line resistance. 
 
Total length of line on one MAPNET channel shall not exceed 3,000 m including all 
T-taps and parallel runs. 
 
Maximum length for ONE continuous MAPNET run is 1200 m for up to 128 MAPNET 
devices using 1.5 mm sq cable. 
 
When the run exceeds 850 m it is necessary to use twisted, shielded pair. 
 
 
 
Copper Line Characteristics 
 
Network "Wired" (formerly called RS-485) Communication wiring shall be 0.75 mm sq 
twisted, shielded pair (TSP), or 0.22 mm sq twisted pair (TP). Shielded Cable is 
recommended for new installations. When shielding is used, the shield shall be connected 
to Earth Ground, at the Left Port end of span only.  
 
No T-tapping of the Network conductors is allowed. Network wiring is point-to-point, 
only. 
 
Maximum line length between ports at 57,600 and 9600 bits per second is shown in the 
table below. 
 
 Maximum 
Wiring 
Distance 
 
Communication Speed 
0.75mm sq TSP Wire.  
 (Maximum capacitance 
between conductors is 174 
pf. per meter) 
0.22mm sq TP Wire.  
(Maximum capacitance 
between conductors is 66 
pf. per meter) 
57,600 bps 
3,000 m 
2,300 m 
9600 bps 
5,600 m 
4,000 m 
 
Table J- 1  Network: Maximum Transmission Distances, "Wired" Network 
 
 
Continued on next page 
Appendix J 
Cable Characteristics 
IDNet 
4100 MAPNET II  
 
NETWORK