Toshiba E6580772 Manual Do Utilizador

Página de 26
E6580772③
10
3. Functional description
In this section, functions added by the installation of this F10M option unit, on top of the standard inverter
functions, are described.
3.1 F10M communication function
 Through the communication network, drive and stop control and concentrated monitoring control of operation
status can be carried out by the programmable controller and industrial computer.
3.1.1 Connection of transmission cable
 
z
  SL1, SL2, SG
 Transmission path is constructed by the shielded twisted pair cables as shown in the figure below.
 Be sure to connect SL1, SL2 and SG mutually to another station. Note that wrong connection will not bring the
correct transmission.
z
 SHD
 Connect a shield of twisted pair cable to the transmission terminal SHD of each station and set up a class 3 or
equivalent grounding work in an arbitrary station.
z
 Terminal 
resistor
 Set terminal resistors at both sides of the system for the sake of impedance matching. Connect terminal
resistor (120Ω-1/2W) between the terminal block SL1 and SL2.
 (As for the master station (MS), terminal resistor can be combined by connecting L1 and TERM.)
 
TERM
L1
L2
SG
FG
SL1
SL2
SG
SHD
SL1
SL2
SG
SHD
SL1
SL2
SG
SHD
MS
TLF0 0 1 Z
TLF0 0 1 Z
TLF0 0 1 Z
Grounding / Earthing
  (Grounding / earthing resistance 100 Ω max.)
Terminal resistor
 120 Ω-1/2W
Shielded twisted pair cable
 Connection of communication cable of TOSLINE F10M
Signal name
Name
Detail
SL1
Transmitting and receiving data
Positive line
SL2
Transmitting and receiving data
Negative line
SG
Signal ground
Ground of signal line
 
Do not connect a grounding line of the shield and a power line earth of the inverter or so.
 
Separate a transmission cable from the main circuit connection wire by more than 200mm.