Omni Group Step Top Wood Stove 57ST-ACC Manual Do Utilizador

Página de 52
November 28, 2011
7038-159D
Page  35
R
5700 Step Top Wood Stove Series ACC
• 
Must  be  a  6  inch  (152mm)  diameter  (ID)  high 
temperature  chimney  listed  to  UL  103  HT  (2100
o
F) 
or ULC S629M.
• 
Must use components required by the manufacturer 
for installation.
• 
Must maintain clearances required by the manufacturer 
for installation.
• 
Refer to manufacturers instructions for installation.
D.  Factory-Built Chimney
The  chimney  can  be  new  or  existing,  and  must  meet  the 
following minimum requirements.
Figure 35.1 - Factory-Built Exterior Chimney
Floor 
Protector 
Chimney  
Connector 
Insulated " T " 
Flashing 
Listed Termination Cap 
Trim Collar on 
Inside Wall 
Listed Chimney 
Storm Collar 
Wall Support 
Roof Brace (if required) 
Floor  
Protector 
Chimney  
Connector 
Ceiling Support 
Listed Chimney 
Listed Termination Cap 
Storm Collar 
Flashing 
NOTICE:
 
In Canada when using a factory-built chim-
ney it must be safety listed, Type UL103 HT (2100
o
F) 
[1149
o
C] CLASS “A” or conforming to CAN/ULC-S629, 
STANDARD FOR 650
o
C FACTORY-BUILT CHIM-
NEYS.
Figure 35.2 - Factory-Built Interior Chimney
WARNING! Risk of Fire!
Inspection of Chimney:
•  Chimney must be in good condition and meets the 
minimum standard of NFPA 211.
•  Factory-built chimney must be 6 inches (152mm) 
UL103 HT.
WARNING! Risk of Asphyxiation!
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE 
SERVING ANOTHER APPLIANCE.
DO NOT CONNECT TO ANY AIR DISTRIBUTION 
DUCT OR SYSTEM.
This may allow fl ue gases to enter the house.