- 7 - 
Step 
Action 
Display 
3. 
To change any of the programming for the wireless key, perform one 
of the following steps in the Programming for an Installation WITH 
Local Wireless Keys
 section. 
•  For the user code, perform step 5. 
•  For the loop functions, perform steps 6 and 7. 
•  For the on-board relay assignment, perform steps 8 to 10. 
Alternately flashes "d*" with the device number; 
and “--.” 
4. 
When you have completed editing the wireless keys, press the [
✻] key 
twice to exit the Program mode
 
* The keypad will display the last number that was enrolled (i.e., “d3”) 
Note:  Upon exiting the Program mode, the 6150RF alternately flashes "Ad," the 2-digit keypad address, and the 2-digit receiver 
address.  If either of these is incorrect, repeat steps 1 through 3 in the Programming for an Installation Without Local Wireless 
Keys
 section. 
TROUBLESHOOTING 
The following error messages cause the 6150RF to produce rapid beeps for 5 seconds. The table below describes the 
error messages and the corrective actions. 
Display 
Probable Cause 
Corrective Action 
Lb 
Low battery in the wireless 
key 
1.  Replace the battery if the wireless key has a replaceable battery. 
2.  Replace the transmitter if the wireless key does not have a replaceable 
battery. 
OC 
Open circuit 
Verify that the Data Out wire is connected properly. 
1C 
Incompatible connection 
Verify that the control panel is not a First Alert-type control panel. 
Check 09 OR 
Check 100 RF 
Receiver OR 
Check 10n RF 
Receiver* 
1.  6150RF Receiver is not 
communicating 
2. 
Another device on the 
keypad terminals is not 
communicating to the 
control panel 
1.  Verify that the Data In wire is connected properly. 
 
2.  Verify the wiring connections between the control and all other devices. 
E8 
Too many RF zones 
programmed 
Verify the number of transmitters programmed into the control panel 
*n = receiver address programmed in VISTA control panel 
 
SPECIFICATIONS
Physical: 
6-1/4” H x 4-7/8” W x 1” D  
 
(158.75mm x 123.8mm x 25.4mm) 
Wiring: 
Refer to Wiring Table on page 2 
Range: 
200' nominal 
Frequency:  345 MHz 
Voltage: 
12VDC 
Current: 
Standby 80mA 
Backlighting on and 
 Sounder 
on 
105mA 
Relay:  
Normally-Open, 1A, 28VDC 
Sounder: 
Piezo-electric (fire alarm is loud pulsing tone; 
burglary/audible panic alarm is two tone 
sound