Warning: Incorrect venturi adjustment may lead to improper combustion, which is a safety hazard. 
Contact the dealer if there is any concern about the venturi adjustment.
NEVER USE AN OPEN FLAME FOR LEAK TESTING
a
iR
 D
iveRteR
 c
ontRoL
:
When the blower is on, the amount of air flow into the room can be adjusted 
with the air diverter. When the lever is  to the far left the room receives the 
air, when the lever is  to the far right the air goes out the duct and when 
the lever in the middle the air goes to both the duct and the room. Lever is 
found above the right end of the control panel, see Figure 5.
Operating Instructions
P
iLot
 L
ight
:
1. Turn off the gas to the fireplace.  If not recently done, remove the glass and let the unit air out 
for at least five (5) minutes to clear out any gas. Turn on gas to the heater. Leak test all joints 
with soapy water. NEVER USE AN OPEN FLAME FOR LEAK TESTING. 
Thermopile
Thermocouple
Figure 3.  Pilot flame.
2. Start the pilot by pressing the gas control knob and turning it to PILOT.  
While  holding  the  gas  control  knob  in,  press  the  piezo  ignitor  several 
times until the pilot light starts. Hold the gas control knob in for thirty 
(30) seconds. Check that the pilot has fully engulfed the thermocouple 
assembly (see Figure 3).
3. Start the main burner by turning the gas control knob to ON and then turn 
the rocker switch to ON. Check that all burner ports have flame.
4. Leak test all gas joints again.
v
entuRi
 a
Djustment
:
The venturi adjustment lever is centered above the control panel.
The venturi allows the amount of air coming into the fireplace to be adjusted in order to accommodate 
different climates and venting arrangements. Start the pilot and then the burner. Make sure the pilot 
flame is burning normally and none of the burner ports are plugged. Let the fireplace burn for roughly 
fifteen (15) minutes and then examine the flames.
The ideal flame will be blue at the base and light orange 
above (see Figure 49). The flames should be of medium 
height.  If the flames look like this, no venturi adjustment 
is  needed.  If  the  flames  are  fairly  short  and  mostly 
blue,  the  fireplace  is  getting  too  much  air.  Therefore, 
the  air  shutter  should  be  closed  (push  in)  slightly  until 
the  correct  flames  are  achieved.    Flames  that  are  very 
orange, with tall dark stringy tips are not getting enough 
air.  Open (pull out) the venturi until the flames clean up.  
If the venturi is opened,  then closed all the way, and the 
correct flames cannot be attained, turn off the gas and 
contact the dealer.
Figure 4.  Venturi Adjustment Lever
7
Figure 5. Air Diverter