Apex Digital 5708009-C Manual Do Utilizador

Página de 160
5708009-C
4-51
Apex 1 to 5.5 kW Generator
162
read 
process 
status
Requests report on process status; returning 
packet contains the following bytes arranged 
as follows.
1st status byte:
0 = unassigned
1 = unassigned
2 = recipe run is active
3 = unassigned
4 = unassigned
5 = output power (0 = off, 1 = on)
6 = RF on requested
7 = setpoint status (0 = within tolerance, 
1 = out of tolerance)
2nd status byte:
0 = end of target life
1 = unassigned
2 = unassigned
3 = overtemperature
4 = unassigned
5 = unassigned
6 = unassigned
7 = interlock open
3rd status byte—fault flags
0 = nonmaskable interrupt
1 = bus fault
2 = high bus voltage
3 = unassigned
4 = low bus voltage
5 = out of setpoint
6 = unassigned interrupt
7 = unassigned
4th status byte—fault flags
0 = current limit
1 = contactor failure
2 = Profibus error
3 = unassigned
4 = unassigned
5 = unassigned
6 = unassigned
7 = CEX is locked
0
4 data bytes
4—8-bit 
values
Table 4-6. Host Port Commands for RS-232 with AE Bus  (Continued)
Command
Description
Number of 
Host Data 
Bytes
Number of 
Response 
Data Bytes