Bacharach GDC-150 Manual Do Proprietário

Página de 28
GDC-150 Operation Manual 
 
 
5209-9000 Rev 0 
 
15 
4.5.  Open Loop Diagnostic 
 
The  GDC-150  circuit board has been fitted with a red LED located near the bottom 
center of the circuit board.  This is an “open loop” indicator and has been designed as 
a quick trouble shooting device.  If the 4-20 mA signal loop has not been connected 
properly or has been damaged in some manner between the analog transmitter and 
the device to which it is sending its signal output, this LED illuminates.  At this point, 
the wiring should be inspected for potential problems. 
 
4.6. Jumper Functions 
 
 
Figure 4-1.  Jumper Functions 
4.7.  Adjusting the Alarm Set Point (For Relay Option Only) 
 
If the optional relay has been supplied, the alarm set point on the GDC-150  can be 
adjusted.  The alarm set point value is converted to a voltage in the range of 0-4 VDC.  
This voltage range correlates to the full measurement range of the installed sensor.   
 
4.7.1.  Calculating the Alarm Set Point Value 
 
Prior to adjusting the alarm set point, calculate the voltage value required using the 
following formula. 
 
 
 
Example:  Catalytic combustible sensors  have  a  standard measurement range of 
0-100% LEL.  Therefore 4.0 VDC = 100% LEL.  Using the values below, 10% of 
4.0 VDC = 0.4 VDC.  Therefore, the required voltage setting to achieve an alarm set 
point of 10% LEL is 0.4 VDC.